GEK-113328A
G650 Generator Protection & Control System
2-27
2 PRODUCT DESCRIPTION
2.4 TECHNICAL SPECIFICATIONS
2
2.4.6.2 AC VOLTAGE INPUTS
2.4.6.3 CONTACT INPUTS
2.4.6.4 ANALOG INPUTS
VT Ratio
1.0 to 6000.0 in steps of 0.1
Rated Voltages
500 Vac
Metering range:
From 2 to 500 Vac
Relay Burden:
0.05 VA at 120 Vac (50 or 60 Hz)
Voltage Withstand:
Continuous at 500 V to neutral
1 min/hr at 800 to neutral
VAC inputs do not need varistors, as the impulse test is applied to 100% of the transformers
Input Activation Voltage Threshold:
10 to 230 Vdc in steps of 1 V (selectable by setting)
Impedance:
> 100 kOhm
Maximum error:
±
10% setting or
±
5 V
Load for voltage supervision inputs:
2 mA + V/100 kOhm
Voltage threshold for voltage
supervision inputs:
< 10 V (fixed)
Debounce Time:
1 to 50 in steps of 1 ms
Recognition time:
< 1ms
Timing resolution:
1 ms
For Input Activation Voltage Threshold and Debounce Time there is a single setting for all inputs in the same group (inputs
sharing the same common).
Input Type and Delay Input Time are not grouped; there is a different setting for each input.
Input Type
Positive-Edge / Negative-Edge / Positive/ Negative
Delay Input Time
0 to 60000 ms in steps of 1 ms (Input signal time delay)
Input impedance
116
Ω
Current Input (mADC):
0 to -1; 0 to +1; -1 to +1; 0 to 5; 0 to 10; 0 to 20; 4 to 20 (programmable)
Conversion Range:
-1 to +20mA
Accuracy:
±
0.2% of full scale
Type:
Passive
Содержание Multilin GEK-113328A
Страница 2: ......
Страница 6: ...4 G650 Generator Protection Control System GEK 113328 TABLE OF CONTENTS ...
Страница 26: ...1 20 G650 Generator Protection Control System GEK 113328A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 170: ...7 6 G650 Generator Protection Control System GEK 113328A 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 185: ...GEK 113328A G650 Generator Protection Control System A 11 APPENDIX A A 1 FACTORY DEFAULT LOGIC A ...
Страница 186: ...A 12 G650 Generator Protection Control System GEK 113328A A 1 FACTORY DEFAULT LOGIC APPENDIXA A ...
Страница 218: ...C 2 G650 Generator Protection Control System GEK 113328A C 1 GE MULTILIN WARRANTY APPENDIXC C ...