SETPOINT > CONTROL ELEMENTS > ACCIDENTAL ENERGIZATION
ACCIDENTAL ENERGIZATION 1 > ACCIDENTAL ENERGIZATION 2 > ACCIDENTAL ENERGIZATION 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Arming mode for Accidental
Energization
Accdnt Enrg Mode
UV AND OFF-LINE N/A
[UV AND OFF-LINE – UV
OR OFF-LINE]
Overcurrent Level to operate
Overcurrent pickup
1.50
0.01 A
[0.00 : 160.00]
Arming undervoltage value
Ph Undervoltage
pickup
40.00
0.01 V
[0.00 : 500.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]