2-24
G650 Generator Protection & Control System
GEK-113328A
2.4 TECHNICAL SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.4.4 USER-PROGRAMMABLE ELEMENTS
2.4.4.1 PLC LOGIC
2.4.4.2 FLEXCURVES
2.4.4.3 USER-PROGRAMMABLE LEDS
Samples
1 sec., 1, 5, 10, 15, 20, 30, 60 min.
Storage Capacity
Fixed, 32768 measures
Programming language:
The logical configuration is performed using graphical functions based on the
IEC 61131-3 standard.
Lines of code:
512
Supported operations:
NOT, XOR, OR (2 to 8 inputs), AND (2 to 8 inputs), NOR (2 to 8 inputs),
NAND (2 to 8 inputs), Latch (Reset Dominant), Edge Detectors, Timers.
2 inputs default gates, from 3 to 8 inputs provided in library format.
Libraries:
Logical gates fully programmable by user. To create user-programmable logic to
be distributed as a single object.
Inputs:
Any logical variable, contact or virtual input
Number of timers:
8 maximum in each logic scheme (provided in library format)
Number:
4 (A through D)
Reset points:
40 (0 through 1 of pickup)
Operate points:
80 (1 through 20 of pickup)
Time delay:
0 to 65535 ms in steps of 1
Saturation Level
20 times the pickup level
Number:
15 configurable LEDs plus a ready non configurable LED
Programmability:
from any logical variable, contact, or virtual input
Reset mode:
Self-reset or Latched.
The first 5 LED’s are latched by hardware (red color ones), usually configured for
trip signals.
The following 10 ones (yellow and green) are self-reset but can be latched
through PLC configuration.
Reset Signal:
The LED’s can be reset by hardware, pressing the front “esc” key during more
than 3 seconds or using the LED reset signal through PLC configuration.
Содержание Multilin GEK-113328A
Страница 2: ......
Страница 6: ...4 G650 Generator Protection Control System GEK 113328 TABLE OF CONTENTS ...
Страница 26: ...1 20 G650 Generator Protection Control System GEK 113328A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 170: ...7 6 G650 Generator Protection Control System GEK 113328A 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 185: ...GEK 113328A G650 Generator Protection Control System A 11 APPENDIX A A 1 FACTORY DEFAULT LOGIC A ...
Страница 186: ...A 12 G650 Generator Protection Control System GEK 113328A A 1 FACTORY DEFAULT LOGIC APPENDIXA A ...
Страница 218: ...C 2 G650 Generator Protection Control System GEK 113328A C 1 GE MULTILIN WARRANTY APPENDIXC C ...