5-12
G650 Generator Protection & Control System
GEK-113328A
5.3 FIRMWARE VERSION UPGRADE
5 BOOTCODE AND FIRMWARE UPGRADE
5
6.
FOLLOW THE INDICATIONS OF THE PROGRAM AND SELECT THE BOOT PROGRAM BIN FILE.
7.
WHEN REQUIRED BY THE PROGRAM SWITCH OFF AND BACK ON THE RELAY.
8.
CONTINUE WITH THE PROCESS AND SET THE IP ADDRESS AND GATEWAY WHEN REQUIRED.
5.3.3 FIRMWARE UPGRADE (*)
1.
INSTALL THE PROPER VERSION OF THE ENERVISTA 650 SETUP PROGRAM.
2.
CONNECT ONE ETHERNET CABLE AT THE REAR ETHERNET PORT (CROSSOVER CABLE FOR BACK-TO-
BACK CONNECTION AND STRAIGHT-THROUGH ETHERNET CABLE FOR HUB OR SWITCH).
3.
SET THE APPROPRIATE IP ADDRESS IN THE RELAY.
4.
SET THE APPROPRIATE IP ADDRESS IN THE PC.
5.
FROM THE ENERVISTA 650 SETUP PROGRAM SELECT “
Communications > Upgrade Firmware Version
”.
6.
ENTER THE IP ADDRESS, SERIAL NUMBER AND ORDERING CODE OF THE RELAY TO UPGRADE.
7.
WHEN REQUIRED BY THE PROGRAM SWITCH OFF AND BACK ON THE RELAY.
8.
LOCATE THE UPGRADE.TXT FILE ACCORDING TO THE MODEL OF THE RELAY.
9.
PRESS UPGRADE FIRMWARE AND INITIATE THE UPGRADE PROCESS.
10. TO COMPLETE THE PROCEDURE, SWITCH OFF AND BACK ON THE RELAY WHEN REQUIRED BY THE
PROGRAM.
11. SET CALIBRATION SETTINGS (FROM THE PC TO THE RELAY).
12. THE SETTINGS AND CONFIGURATION ARE NOW SET TO FACTORY DEFAULT.
13. SEND THE NEW SETTINGS AND CONFIGURATION FILES TO THE RELAY IF NECESSARY.
(*) The boot code upgrade must be performed using a crossed copper cable (RJ45) connected to the PC. It is not
necessary to modify the internal fiber/cable switch, as the upgrade is carried out at 10 Mb/s, and thus there is not cable/
fiber conflict.This fact does not apply to the firmware upgrade, which can be performed either with the Ethernet fiber
connection, or with the cable connection.
Note: Please see chapter 8 TROUBLESHOOTING GUIDE if there is any problem during the upgrading process.
Содержание Multilin GEK-113328A
Страница 2: ......
Страница 6: ...4 G650 Generator Protection Control System GEK 113328 TABLE OF CONTENTS ...
Страница 26: ...1 20 G650 Generator Protection Control System GEK 113328A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 170: ...7 6 G650 Generator Protection Control System GEK 113328A 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 185: ...GEK 113328A G650 Generator Protection Control System A 11 APPENDIX A A 1 FACTORY DEFAULT LOGIC A ...
Страница 186: ...A 12 G650 Generator Protection Control System GEK 113328A A 1 FACTORY DEFAULT LOGIC APPENDIXA A ...
Страница 218: ...C 2 G650 Generator Protection Control System GEK 113328A C 1 GE MULTILIN WARRANTY APPENDIXC C ...