GEK-113328A
G650 Generator Protection & Control System
B-7
APPENDIX B
B.1 FACTORY DEFAULT SETTINGS
B
SETPOINT > SYSTEM SETUP > BREAKER > BREAKER SETTINGS
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Number of Switchgear selected as
breaker
Number of Switchgear 1
1
[1 : 16]
Maximum value of KI2t
Maximum KI2t
9999.99
0.01(KA)2
s
[0.00 : 9999.99]
KI2t integration time
KI2t Integ. Time
0.03
0.01s
[0.03 : 0.25]
Maximum number of openings
Maximum Openings
9999
1
[0 : 9999]
Maximum Openings in one hour
Max.Openings 1 hour
40
1
[1 : 60]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > SYSTEM SETUP > BREAKER > BREAKER MAINTENANCE
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
KI2t Counter Phase A
KI2t BKR Ph A Cnt
0.00
0.01 (KA)2
s
[0.00 : 9999.99]
KI2t Counter Phase B
KI2t BKR Ph B Cnt
0.00
0.01 (KA)2
s
[0.00 : 9999.99]
KI2t Counter Phase C
KI2t BKR Ph C Cnt
0.00
0.01 (KA)2
s
[0.00 : 9999.99]
Openings counter
BKR Openings Cnt
0
1
[0 : 9999]
Closings counter
BKR Closings Cnt
0
1
[0 : 9999]
SETPOINT > SYSTEM SETUP > SWITCHGEAR
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Snapshot Event generation for
switchgear #1
Snapshot Events
SWGR 1
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #2
Snapshot Events
SWGR 2
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #3
Snapshot Events
SWGR 3
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #4
Snapshot Events
SWGR 4
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #5
Snapshot Events
SWGR 5
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #6
Snapshot Events
SWGR 6
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #7
Snapshot Events
SWGR 7
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #8
Snapshot Events
SWGR 8
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #9
Snapshot Events
SWGR 9
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #10
Snapshot Events
SWGR 10
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #11
Snapshot Events
SWGR 11
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #12
Snapshot Events
SWGR 12
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #13
Snapshot Events
SWGR 13
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #14
Snapshot Events
SWGR 14
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #15
Snapshot Events
SWGR 15
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation for
switchgear #16
Snapshot Events
SWGR 16
DISABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin GEK-113328A
Страница 2: ......
Страница 6: ...4 G650 Generator Protection Control System GEK 113328 TABLE OF CONTENTS ...
Страница 26: ...1 20 G650 Generator Protection Control System GEK 113328A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 170: ...7 6 G650 Generator Protection Control System GEK 113328A 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 185: ...GEK 113328A G650 Generator Protection Control System A 11 APPENDIX A A 1 FACTORY DEFAULT LOGIC A ...
Страница 186: ...A 12 G650 Generator Protection Control System GEK 113328A A 1 FACTORY DEFAULT LOGIC APPENDIXA A ...
Страница 218: ...C 2 G650 Generator Protection Control System GEK 113328A C 1 GE MULTILIN WARRANTY APPENDIXC C ...