GE Multilin
Sub Meters
20
2.2. Setup (Program)
The Meter must be Set (programmed/configured) to match the application settings, before
use. Otherwise, the readings will be wrong. All the Setup values can be re-programmed at any
time, upon entering “SET” However, the settings: Sys (Star/wye or Delta), Vpri, Vsec, Apri,
Asec critically determine the scaling of measured readings. While the scaling may be used to
tune out Instrument Transformer errors, wrong settings will upset the readings of running
systems. It is the user’s responsibility to ensure that only qualified personnel correctly Set-up
the Meter.
Action
Display
Remarks
From the “RMS” or “INTG”
page, go Up
Then go Left .
"Code
y
" is displayed. “
y
"
blinks.
Prog
"Code
y
"
The meter is about to enter the Main Menu. “
y
" blinks.
To proceed with Code Entry, we need to enter the Main
Menu.
•
Go Left .
Or,
to abort and re-enter RMS:
•
Press .
Or, to only view setup, (no edit):
•
Press or to toggle “
y
” to “
n
".
•
Press to enter Main Menu.
•
"Fail" is flashed, then "run" is displayed.
To proceed with Code Entry: "000
0
" The
blinking
digit indicates the cursor.
The code is Factory Set to
1000. Press to enter each
digit. Three times totally.
"
2
000" We have now entered the Units, Tens and Hundreds digits.
The Thousands digit needs to be changed from 2 to 1.
Press to decrement “
2
".
"
1
000" Now the Code of 1000 is almost in.
Press to enter the Main
Menu.
"
0000"
“Pass”
“run”
Or,
“Fail”
Notice that a “0” quickly hides each code-digit you enter.
“run” indicates a successful entry into the Main Menu.
Congratulations!
If you were not successful, don’t despair; you can have
another go from the top of this Table! Briefly switching off
the Meter will easily return you to the RMS page, the starting
point.
Now press
Again press
“CLR”
“SET”
You are at the Setup page.
Press to get into “SET”
“2000” You’ve now entered the Setup Menu. The first two entries are
the Model Number and firmware version for easy
identification.
Go to see other Settings.
Go to see and change their values.
Once you’re done, re-trace
your path: and .
Remember “Save Y”
“run” You’re now back to the top of the Main Menu. Go . You’ll
see RMS. You can now go or to view all the display
pages.