GE Multilin
Sub Meters
18
Code
Note 1.
Name
Description
Clr
Intg
Intg
y / n
t
o
Clear
Clr = Clear. If "y", Clears all integrator parameters (above) to zero.
Set
Save
y / n
2000
03.01.
01.00
SYS
V.PRI
V.SEC
A.PRI
A.SEC
LAbL
VA.Fn
baud
Prty
Id
2000
03.01.
01.00
StAR
415.0
415.0
100.0
5.000
123
3d
9600
EVn.1
1.000
to Edit
Setting
Model = 2000. non editable.
Version = 03.01.01. non editable.
SYS = Power system's configuration* : Star (3E 4V3A), Delta (3E 3V2A)
V.PRI = Voltage primary winding(PT) * : Line to Line: 100V to 999kV(415.0)
V.SEC = Voltage secondary winding(PT)* : Line to Line : 50V to 601V (415.0)
A.PRI = Current primary winding.(CT)* : 1A to 99kA (0100)
A.SEC = Current secondary winding.(CT)* : 1A to 6.5A. (5.000)
LAbL = Phase labeling formats. : 123, ryb, rst, Pqr, Abc.
VA.Fn = VA function selection : 3d, Arth
baud = Baud rate : 1200, 2400, 4800, 9600, 19200.
Prty = Parity and Stop bit settings : EVn.1, EVn.2, Odd.1, Odd.2, no.1, no.2
Id = RS485 Device ID number : 001 to 247. (Evn.1 = Even. 1 stop bit)
*changing these values while the device in use, is not recommended
dIAG Id
baud
Prty
1.000
9600
Evn.1
For factory testing only
dIA2
Mdl
Ver
Ver
2000
03.01.
01.00
For factory testing only
NOTES:
1. To “Clear” Integrated values or “Set” meter settings, you must first enter the Main Menu.
•
Go Left to the “RUN” page from "PROG"
.
•
You must now enter the Factory Set code of 1000, to proceed.
o
"Code y”, followed by the entry of the Code “1000" is required.
o
To enter the code, edit the blinking digit value Up or Down to get “1000”.
o
Keep going Left.
o
Without entering the code, you may view the settings, but you can’t change
them.
2. Within the “SET” page options, the Factory settings are shown Bold Text in the right side
column above.
2.1.1. Auto-Scroll
Auto-Scroll allows you to monitor a group of Display Pages sequentially, every 5 seconds,
without constant key pressing. This is convenient for viewing from a distance. Since the EPM
2000 displays the Parameter Name(1sec) followed by the Value(4 sec) on the same large
displays, both are equally readable from a distance. No more squinting at a clutter of
parameter indicators.
To enter auto-scroll, go to the desired display page and keep the Up or Down key
pressed for minimum 3 seconds. The display flashes “Auto” and then automatically scrolls
through other pages at the same level (column in the above table). Press any key to revert to
Manual Scrolling.
•
The Up key enters Limited Auto-scroll – within the same Group, eg only “RMS” or
only “INTEG”.
•
The Down key enters Full Auto-scroll- down the entire column of pages.