1.3.2. Standard Measurements
The EPM 2000 can measure, locally display and remotely transfer over MODBUS RTU, the
following electrical parameters over the input range with an accuracy of 0.5% or better for
Volts and Amps and 1% for Power and Energy functions:
Amps: 50mA – 6A, Overload: 10A continuous, 50A for 3 seconds.
Volts: 80- 600V Phase - Phase and 48 - 347 V Phase – Neutral
Burden (Load): 0.2VA per Volts / Amps input
Frequency: 45 – 65 Hz
•
True RMS voltage phase to neutral and 3phase average.
•
True RMS voltage phase to phase and 3phase average.
•
True RMS current per phase and 3phase average.
•
Real Power and Energy.
•
Reactive Power and Energy.
•
Apparent Power and Energy.
•
Power Factor.
•
Frequency.
The EPM 2000 provides all single phase (per-phase) Real, Apparent, Reactive Power and
Power Factor values. Positive (Inductive) and Negative (Capacitive) Reactive Energy is
separately accumulated for Lead / Lag analysis.
1.3.3. Accuracy
Measurement
Class 1.0, % of reading
•
Voltage LN, per phase
0.5
•
Voltage LL, per phase
0.5
•
Voltage LN, avg
0.5
•
Voltage LL, avg
0.5
•
Amp, per phase
0.5
•
Amp, avg
0.5
•
Amp, Phase Angle per phase
2º
•
Frequency
0.1
•
Real Power, (kW) Per Phase & Total
1.0
•
Reactive Power, (kVAR) Per Phase &
Total
2.0
•
Apparent Power, (kVA) Per Phase &
Total
1.0
•
Power factor, Per Phase & average
1.0
•
Active Energy, (kWh) Import/Export
1.0
•
Reactive Energy, (kVARh) (Ind / Cap)
2.0
•
Apparent Energy, (kVAh)
1.0
* Additional error of 0.05 % of full scale for meter input current below 100 mA.