489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 7: TESTING
7.3.10 Voltage Restrained Overcurrent Accuracy
Setup the relay as shown in FIGURE 7–3:
Secondary Injection Test Setup #3
Z
In the
S2 SYSTEM SETUP
ZV
GEN. PARAMETERS
menu, set:
GENERATOR RATED MVA:
“100 MVA”
GENERATOR VOLTAGE PHASE-PHASE:
“12000”
Z
In the
S2 SYSTEM SETUP
ZV
VOLTAGE SENSING
menu, set:
VT CONNECTION TYPE:
“Open Delta”
VOLTAGE TRANSFORMER RATIO:
“100:1”
Z
In the
S5 CURRENT ELEMENTS
Z
OVERCURRENT ALARM
menu, set:
OVERCURRENT ALARM:
“Unlatched”
O/C ALARM LEVEL:
“1.10 x FLA”
OVERCURRENT ALARM DELAY:
“2 s”
O/C ALARM EVENTS:
“On”
Z
In the
S5 CURRENT ELEMENTS
ZV
PHASE OVERCURRENT
menu, set:
PHASE OVERCURRENT TRIP:
“Latched”
ENABLE VOLTAGE RESTRAINT:
“Yes”
PHASE O/C PICKUP:
“1.5 x CT”
CURVE SHAPE:
“ANSI Extremely Inv.”
O/C CURVE MULTIPLIER:
“2.00”
O/C CURVE RESET:
“Instantaneous”
The trip time for the extremely inverse ANSI curve is given as:
(EQ 7.8)
where:
M
=
O/C CURVE MULTIPLIER
setpoint
I
= input current
I
p
=
PHASE O/C PICKUP
setpoint
A
,
B
,
C
,
D
,
E
= curve constants, where A = 0.0399,
B
= 0.2294,
C
= 0.5000,
D
= 3.0094,
and
E
= 0.7222
K
= voltage restrained multiplier <optional>
The voltage restrained multiplier is calculated as:
(EQ 7.9)
and has a range of 0.1 to 0.9.
Z
Secondary Injection Test Setup #3
on page 7–19, inject current
and apply voltage as per the table below.
Z
Verify the alarm/trip elements and view the event records in the
A5
EVENT RECORD
menu.
Time to Trip
M
A
B
I
K
〈 〉
I
p
×
-------------------
C
–
-----------------------------
D
I
K
〈 〉
I
p
×
-------------------
C
–
⎝
⎠
⎛
⎞
2
-------------------------------------
E
I
K
〈 〉
I
p
×
-------------------
C
–
⎝
⎠
⎛
⎞
3
-------------------------------------
+
+
+
⎝
⎠
⎜
⎟
⎜
⎟
⎜
⎟
⎛
⎞
×
=
K
phase-to-phase voltage
rated phase-to-phase voltage
---------------------------------------------------------------------------
=