489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
5.1.4
Dual Setpoints
The 489 has dual settings for the current, voltage, power, RTD, and thermal model
protection elements (setpoints pages S5 to S9). These setpoints are organized in two
groups: the main group (Group 1) and the alternate group (Group 2). Only one group of
settings is active in the protection scheme at a time. The active group can be selected
using the
ACTIVATE SETPOINT GROUP
setpoint or an assigned digital input in the S3 Digital
Inputs setpoints page. The LED indicator on the faceplate of the 489 will indicate when the
alternate setpoints are active in the protection scheme. Independently, the setpoints in
either group can be viewed and/or edited using the
EDIT SETPOINT GROUP
setpoint.
Headers for each setpoint message subgroup that has dual settings will be denoted by a
superscript number indicating which setpoint group is being viewed or edited. Also, when a
setpoint that has dual settings is stored, the flash message that appears will indicate
which setpoint group setting has been changed.
If only one setting group is required, edit and activate only Group 1 (that is, do not assign a
digital input to Dual Setpoints, and do not alter the
ACTIVATE SETPOINT GROUP
setpoint or
EDIT SETPOINT GROUP
setpoint in
S3 DIGITAL INPUTS
).
5.1.5
Commissioning
Tables for recording of 489 programmed setpoints are available as a Microsoft Word
document from the GE Multilin website at
. See the Support
Documents section of the 489 Generator Management Relay page for the latest version.
This document is also available in print from the GE Multilin literature department (request
publication number GET-8445).