6–16
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
6.3
A2 Metering Data
6.3.1
Current Metering
PATH: ACTUAL VALUES
ZV
A2 METERING DATA
Z
CURRENT METERING
CURRENT
[
Z
]
A:
0
B:
0
C:
0
Amps
Range: 0 to 999999 A
MESSAGE
a:
0
b:
0
c:
0
Neut.Amps
Range: 0 to 999999 A
MESSAGE
a:
0
b:
0
c:
0
Diff.Amps
Range: 0 to 999999 A
MESSAGE
AVERAGE PHASE
CURRENT: 0 Amps
Range: 0 to 999999 A
MESSAGE
GENERATOR LOAD:
0% FLA
Range: 0 to 2000% FLA
MESSAGE
NEGATIVE SEQUENCE
CURRENT: 0% FLA
Range: 0 to 2000% FLA
MESSAGE
PHASE A CURRENT:
0 A
0° Lag
Range: 0 to 999999 A, 0 to 359°
MESSAGE
PHASE B CURRENT:
0 A
0° Lag
Range: 0 to 999999 A, 0 to 359°
MESSAGE
PHASE C CURRENT:
0 A
0° Lag
Range: 0 to 999999 A, 0 to 359°
MESSAGE
NEUT. END A CURRENT:
0 A
0° Lag
Range: 0 to 999999 A, 0 to 359°
MESSAGE
NEUT. END B CURRENT:
0 A
0° Lag
Range: 0 to 999999 A, 0 to 359°
MESSAGE
NEUT. END C CURRENT:
0 A
0° Lag
Range: 0 to 999999 A, 0 to 359°
MESSAGE
DIFF. A CURRENT:
0 A
0° Lag
Range: 0 to 999999 A, 0 to 359°
MESSAGE
DIFF. B CURRENT:
0 A
0° Lag
Range: 0 to 999999 A, 0 to 359°
MESSAGE
DIFF. C CURRENT:
0 A
0° Lag
Range: 0 to 999999 A, 0 to 359°
MESSAGE
GROUND CURRENT:
0.0 A
0° Lag
Range: 0.0 to 200000.0 A, 0 to 359°.
Seen only if 1 A or 5 A Ground
CT is used
MESSAGE
GROUND CURRENT:
0.00 A
0° Lag
Range: 0.00 to 100.00 A, 0 to 359°.
Seen only if 50:0.025 CT is used