CHAPTER 7: TESTING
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
7–19
7.3.9
Injection Test Setup #3
Setup the 489 device as follows for the Voltage Restrained Overcurrent test.
FIGURE 7–3: Secondary Injection Test Setup #3
Test
Phase A
Phase B
Phase C
operate
restrain
operate
restrain
operate
restrain
Slope 1
I
x
I
y
Operation
(OK/not
OK)
Slope 2
I
x
I
y
Operation
(OK/not
OK)
Directional
Check
I
x
N/A
N/A
N/A
I
y
N/A
N/A
N/A
Operation
(OK/not
OK)
N/A
N/A
N/A
E10
V
NEUTRAL
1A
HGF
1A/5A
1A/5A
1A/5A
1A/5A
1A/5A
1A/5A
COM
COM
COM
COM
COM
PHASE a PHASE b PHASE c
PHASE A PHASE B PHASE C
COM
COM
COM
Va
Vb
Vcom
Vc
H9
G3
G6
H4
H7
H1
F10
A
B
C
N
A
B
C
N
V V V V
I
I
I
I
3 PHASE VARIABLE AC TEST SET
GROUND INPUTS
NEUTRAL END CT's
OUTPUT CT's
808822A2.CDR
PHASE
VOLTAGE INPUTS
G10
H3
H6
G5
G8
H2
G9
H10
G4
G7
G2
H5
H8
G1
AUTOMATIC CT
SHORTING
BAR
VC
VA
VB