![GE Multilin 489 Скачать руководство пользователя страница 231](http://html.mh-extra.com/html/ge/multilin-489/multilin-489_instruction-manual_123013231.webp)
CHAPTER 6: ACTUAL VALUES
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
6–17
All measured current values are displayed here.
A, B, C AMPS
represent the output side CT
measurements:
A, B, C NEUT. AMPS
the neutral end CT measurements, and
A, B, C DIFF. AMPS
the differential operating current calculated as the vector difference between the output
side and the neutral end CT measurements on a per phase basis. The 489 negative-
sequence current is defined as the ratio of negative-sequence current to generator rated
FLA,
I
2
/ FLA
×
100%. The generator full load amps is calculated as: generator rated MVA /
(
×
generator phase-to-phase voltage). Polar coordinates for measured currents are
also shown using Va (wye connection) or Vab (open delta connection) as a zero angle
reference vector. In the absence of a voltage signal (Va or Vab), the IA output current is
used as the zero angle reference vector.
6.3.2
Voltage Metering
PATH: ACTUAL VALUES
ZV
A2 METERING DATA
ZV
VOLTAGE METERING
3
VOLTAGE
[
Z
]
Vab:
0
Vbc:
0
Vca:
0
Volts
Range: 0 to 50000 V. Not seen if
VT
CONNECTION
is “None”.
MESSAGE
AVERAGE LINE
VOLTAGE: 0 Volts
Range: 0 to 50000 V. Not seen if
VT
CONNECTION
is “None”.
MESSAGE
Van:
0
Vbn:
0
Vcn:
0
Volts
Range: 0 to 50000 V. Not seen if
VT
CONNECTION
is “Wye”.
MESSAGE
AVERAGE PHASE
VOLTAGE: 0 Volts
Range: 0 to 50000 V. Not seen if
VT
CONNECTION
is “Wye”.
MESSAGE
LINE A-B VOLTAGE:
0 V
0° Lag
Range: 0 to 50000 V, 0 to 359°. Not
seen if
VT CONNECTION
is
“None”.
MESSAGE
LINE B-C VOLTAGE:
0 V
0° Lag
Range: as above
MESSAGE
LINE C-A VOLTAGE:
0 V
0° Lag
Range: as above
MESSAGE
PHASE A-N VOLTAGE:
0 V
0° Lag
Range: 0 to 50000 V, 0 to 359°. Not
seen if
VT CONNECTION
is
“Wye”.
MESSAGE
PHASE B-N VOLTAGE:
0 V
0° Lag
Range: as above
MESSAGE
PHASE C-N VOLTAGE:
0 V
0° Lag
Range: as above
MESSAGE
PER UNIT MEASUREMENT
OF V/Hz: 0.00
Range: 0.00 to 2.00. Not seen if
VT
CONNECTION
is “None”.
MESSAGE
FREQUENCY:
0.00 Hz
Range: 0.00 to 90.00 Hz. Not seen if
VT
CONNECTION
is “None”.
MESSAGE
NEUTRAL VOLTAGE
FUND: 0.0 V
Range: 0.0 to 25000.0 V. Seen only if
there is a neutral VT.
Содержание Multilin 489
Страница 3: ...Courtesy of NationalSwitchgear com ...
Страница 4: ...Courtesy of NationalSwitchgear com ...
Страница 110: ...4 48 489 GENERATOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 4 INTERFACES Courtesy of NationalSwitchgear com ...
Страница 272: ...7 22 489 GENERATOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING Courtesy of NationalSwitchgear com ...