Ethernet Communications
The following setpoints appear when the relay is ordered with the Ethernet (T) option.
PATH: SETPOINTS
Z
S1 489 SETUP
ZV
COMMUNICATIONS
The IP addresses are used with the Modbus protocol. Enter the dedicated IP, subnet IP, and
gateway IP addresses provided by the network administrator.
To ensure optimal response from the relay, the typical connection timeout should be set as
indicated in the following table:
Note
The RS485 COM2 port is disabled if the Ethernet option is ordered.
5.2.4
Real Time Clock
PATH: SETPOINTS
Z
S1 489 SETUP
ZV
REAL TIME CLOCK
For events that are recorded by the event recorder to be correctly time/date stamped, the
correct time and date must be entered. A battery backed internal clock runs continuously
even when power is off. It has the same accuracy as an electronic watch approximately ±1
minute per month. It must be periodically corrected either manually through the front
COMMUNICATIONS
[
Z
]
SLAVE ADDRESS:
254
Range: 1 to 254 in steps of 1
MESSAGE
COMPUTER RS485
BAUD RATE: 9600
Range: 300, 1200, 2400, 4800, 9600,
19200
MESSAGE
COMPUTER RS485
PARITY: None
Range: None, Odd, Even
MESSAGE
FRONT PORT RS232
BAUD RATE: 19200
Range: 300, 1200, 2400, 4800, 9600,
19200
MESSAGE
IP ADDRESS:
0.0.0.0
Range: standard IP address format
MESSAGE
SUBNET IP MASK:
255.255.255.000
Range: standard IP address format
MESSAGE
GATEWAY IP ADDRESS:
0.0.0.0
Range: standard IP address format
TCP/IP sessions
Timeout setting
up to 2
2 seconds
up to 4
3 seconds
REAL TIME
[
Z
]
CLOCK
DATE (MM, DD, YYYY):
01/01/1995
Range: 01/01/1995 to 12/31/2094
MESSAGE
TIME (HH.MM.SS):
12:00:00
Range: 00:00:00 to 23:59:59
MESSAGE
IRIG-B SIGNAL TYPE:
NONE
Range: None, DC Shift, Amplitude
Modulated