489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
5.6.7
Ground Overcurrent
PATH: SETPOINTS
ZV
S5 CURRENT ELEM.
ZV
GROUND OVERCURRENT
The 489 ground overcurrent feature consists of both an alarm and a trip element. The
magnitude of measured ground current is used to time out against the definite time alarm
or inverse time curve trip. The 489 inverse time curve for this element may be either ANSI,
IEC, or GE Type IAC standard curve shapes. This allows for simplified coordination with
downstream devices. If however, none of these curves shapes is adequate, the FlexCurve™
may be used to customize the inverse time curve characteristics. If the Ground CT is
selected as “None”, the ground overcurrent protection is disabled.
Note
The pickup level for the ground current elements is programmable as a multiple of the
CT. The 50:0.025 CT is intended for very sensitive detection of ground faults and its
nominal CT rating for the 489 is 50:0.025.
1 GROUND
[
Z
]
OVERCURRENT
GROUND OVERCURRENT
ALARM: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to
5
MESSAGE
GROUND O/C ALARM
PICKUP: 0.20 x CT
Range: 0.05 to 20.00
×
CT in steps of
0.01
MESSAGE
GROUND O/C ALARM
DELAY: 0 cycles
Range: 0 to 100 cycles in steps of 1
MESSAGE
GROUND OVERCURRENT
ALARM EVENTS: Off
Range: On, Off
MESSAGE
GROUND OVERCURRENT
TRIP: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN TRIP
RELAYS (1-4): 1---
Range: Any combination of Relays 1 to
4
MESSAGE
GROUND O/C TRIP
PICKUP: 0.20 x CT
Range: 0.05 to 20.00
×
CT in steps of
0.01
MESSAGE
CURVE SHAPE:
ANSI Extremely Inv.
Range: see Table 5–1: 489 Overcurrent
MESSAGE
FLEXCURVE TRIP TIME
AT 1.03 x PU: 65535 ms
Range: 0 to 65535 ms. Seen only if
CURVE SHAPE
is Flexcurve
MESSAGE
FLEXCURVE TRIP TIME
AT 1.05 x PU: 65535 ms
Range: 0 to 65535 ms. Seen only if
CURVE SHAPE
is Flexcurve
↓
MESSAGE
FLEXCURVE TRIP TIME
AT 20.0 x PU: 65535 ms
Range: 0 to 65535 ms. Seen only if
CURVE SHAPE
is Flexcurve
MESSAGE
OVERCURRENT CURVE
MULTIPLIER: 1.00
Range: 0.00 to 1000.00 in steps of 0.01
MESSAGE
OVERCURRENT CURVE
RESET: Instantaneous
Range: Instantaneous, Linear