![GE Multilin 489 Скачать руководство пользователя страница 242](http://html.mh-extra.com/html/ge/multilin-489/multilin-489_instruction-manual_123013242.webp)
6–28
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
6.6
A5 Event Recorder
6.6.1
Event Recorder
PATH: ACTUAL VALUES
ZV
A5 EVENT RECORDER
ZV
E001(E256)
E001
[
Z
]
<Cause>
TIME OF E001:
00:00:00.0
Range: hour: minutes: seconds
MESSAGE
DATE OF E001:
Jan. 01, 1992
Range: month day, year
MESSAGE
ACTIVE
GROUP E001: 1
Range: 1, 2
MESSAGE
TACHOMETER
E001: 3600 RPM
Range: 0 to 3600 RPM. Seen only if a
Digital Input set as Tachometer
MESSAGE
A:
0
B:
0
C:
0
A
E001
Range: 0 to 999999 A
MESSAGE
a:
0
b:
0
c:
0
NA
E001
Range: 0 to 999999 NA. Represents
neutral end current.
MESSAGE
NEG. SEQ. CURRENT
E001: 0% FLA
Range: 0 to 2000% FLA
MESSAGE
GROUND CURRENT
E001: 0.00 A
Range: 0 to 20000.0 A. Not seen if
GROUND CT TYPE
is
“None”
.
MESSAGE
Vab:
0
Vbc:
0
Vca:
0
V
E001
Range: 0 to 50000 V. Not seen if
VT
CONNECTION
is
“None”
.
MESSAGE
FREQUENCY
E001: 0.00 Hz
Range: 0.00 to 90.00 Hz. Not seen if
VT
CONNECTION
is
“None”
.
MESSAGE
NEUTRAL VOLT (FUND)
E001:
0.0 V
Range: 0.0 to 25000.0 V. Seen only if
there is a neutral VT.
MESSAGE
NEUTRAL VOLT (3rd)
E001:
0.0 V
Range: 0.0 to 25000.0 V. Seen only if
there is a neutral VT.
MESSAGE
Vab/Iab E001:
0.0
Ω
sec.
0°
Range: 0.0 to 6553.5
Ω
sec., 0 to 359°.
Seen only if the Loss of
Excitation element is Enabled.
MESSAGE
REAL POWER (MW)
E001:
0.000
Range: 0 to ±2000.000 MW. Not seen if
VT CONNECTION
is
“None”
MESSAGE
REACTIVE POWER Mvar
E001:
0.000
Range: 0 to ±2000.000 Mvar. Not seen
if
VT CONNECTION
is
“None”
MESSAGE
APPARENT POWER MVA
E001:
0.000
Range: 0 to 2000.000 MVA. Not seen if
VT CONNECTION
is
“None”
MESSAGE
HOTTEST STATOR
RTD#1: 0°C
E001
Range: –50 to +250°C. Seen only if 1 or
more RTDs are set as Stator.
MESSAGE
HOTTEST BEARING
RTD#7: 0°C
E001
Range: –50 to +250°C. Seen only if 1 or
more RTDs are set as Bearing.