CHAPTER 8: MODBUS MEMORY MAP
MODBUS MEMORY MAP
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
8–7
30683
2AA
VA1 ANGLE
0
359
1
°
F1
---
1
30684
2AB
VB1 ANGLE
0
359
1
°
F1
---
1
30685
2AC
VC1 ANGLE
0
359
1
°
F1
---
1
30686
2AD
Van
0
65535
1
V
F1
---
1
30687
2AE
Vbn
0
65535
1
V
F1
---
1
30688
2AF
Vcn
0
65535
1
V
F1
---
1
30689
2B0
Freq
0
12000
1
Hz
F3
---
1
30690
2B1
Power Factor
-99
100
1
---
F21
---
1
30691
2B2
Real Power
-1000000000 1000000000 1
kW
F13
---
2
30693
2B4
Reactive Power
-1000000000 1000000000 1
kvar
F13
---
2
30695
2B6
Apparent Power
0
1000000000 1
kVA
F2
---
2
EVENT DETAILS
30697
2B8
PH A THERMAL CAP
0
1500
1
%
F2
---
1
30698
2B9
PH B THERMAL CAP
0
1500
1
%
F2
---
1
30699
2BA
PH C THERMAL CAP
0
1500
1
%
F2
---
1
EVENT RECORDER DETAILS
30701
2BC
Neutral Current
0
100000
1
A
F10
---
2
EVENT RECORDER
30703
2BE
Self-Test Event
0
0xFFFFFFFF
2
---
FC188
---
2
EVENT RECORDER DETAILS
30705
2C0
SGround Current
0
6000
1
A
F3
---
2
TRANSIENT RECORDER
30707
2C2
Transient Recorder Last Cleared
0x010107D8 0X0C1F082E 0
---
F18
---
2
30709
2C4
Transient Recorder Available
Records
0
6
1
---
F1
---
1
30710
2C5
Trigger Date
0x010107D8 0X0C1F082E 0
---
F18
---
2
30712
2C7
Trigger Time
0
0X173B3B63 0
---
F19
---
2
30714
2C9
Trigger Cause
0
0xD002
0
---
FC133
---
1
30715
2CA
Trigger Frequency
0
12000
1
Hz
F3
---
1
30716
2CB
Total Triggers
0
0xFFFF
1
---
F1
---
1
30718
2CD
Trigger Position
0
6143
1
---
F1
---
1
30719
2CE
Trace Memory Start Index
0
6143
1
---
F1
---
1
TRANSIENT RECORDER SAMPLES
30720
2CF
Sample Index + Trace Memory
Sample 1
-32767
32767
1
---
F4
---
1
30721
2D0
Sample Index + Trace Memory
Sample 2
-32767
32767
1
---
F4
---
1
30722
2D1
Sample Index + Trace Memory
Sample 3
-32767
32767
1
---
F4
---
1
30723
2D2
Sample Index + Trace Memory
Sample 4
-32767
32767
1
---
F4
---
1
30724
2D3
Sample Index + Trace Memory
Sample 5
-32767
32767
1
---
F4
---
1
30725
2D4
Sample Index + Trace Memory
Sample 6
-32767
32767
1
---
F4
---
1
30726
2D5
Sample Index + Trace Memory
Sample 7
-32767
32767
1
---
F4
---
1
30727
2D6
Sample Index + Trace Memory
Sample 8
-32767
32767
1
---
F4
---
1
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
Содержание ML Series 350
Страница 4: ......
Страница 8: ...iv 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE ...
Страница 10: ...1 2 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 1 COMMUNICATIONS INTERFACES ...
Страница 108: ...4 38 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE SR3 IEC 61850 GOOSE DETAILS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 138: ...4 68 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE IEC 61850 COMMON DATA CLASS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 148: ...5 10 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE OPC UA POINT LISTS CHAPTER 5 OPC UA COMMUNICATION STANDARD ...
Страница 152: ...6 4 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 6 USB INTERFACE ...