4–20
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
SR3 GOOSE CONFIGURATION VIA THE IEC 61850 CONFIGURATOR
CHAPTER 4: SR3 IEC61850 GOOSE
The SR3 Contact I/O, and Virtual Inputs, and the status of Logic Elements are not data
types defined within IEC61850. The GGIO logical nodes are used to map none IEC61850
data into IEC61850 as “general generic” data which is defined within the IEC61850
standard. The SR3 Contact I/O, Virtual Inputs and the status of Logic Elements are mapped
into GGIO2, 3 and 4 respectively.
Let’s take a moment to examine this further before moving on. We will take Virtual Inputs
as our example: