9–6
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
FUNCTION CODE 10H
CHAPTER 9: MODBUS FUNCTIONS
Function Code 10H
Modbus Implementation: Preset Multiple Registers
350 Implementation: Store Multiple Setpoints
This function code allows multiple Setpoints to be stored into the 350 memory. Modbus
“registers” are 16-bit (two byte) values transmitted high order byte first. Thus all
350 setpoints are sent as two bytes. The maximum number of Setpoints that can be stored
in one transmission is dependent on the slave device. Modbus allows up to a maximum of
60 holding registers to be stored. The 350 response to this function code is to echo the
slave address, function code, starting address, the number of Setpoints stored, and the
CRC.
For example, consider a request for slave 17 to store the value 00 02 to setpoint address 04
5C and the value 01 F4 to setpoint address 04 5D. After the transmission in this example is
complete, 350 slave 17 will have the following setpoints information stored:
The master/slave packets have the following format:
Table 9-8: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 10H
Address
Data
04 5C
00 02
04 5D
01 F4
MASTER TRANSMISSION
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message for slave 17
FUNCTION CODE
1
10
store setpoints
DATA STARTING ADDRESS
2
04 5C
setpoint address 04
5C
NUMBER OF SETPOINTS
2
00 02
2 setpoints = 4 bytes
total
BYTE COUNT
1
04
4 bytes of data
DATA 1
2
00 02
data for setpoint
address 04 5C
DATA 2
2
01 F4
data for setpoint
address 04 5D
CRC
2
31 11
CRC error code
SLAVE RESPONSE
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message from slave
17
FUNCTION CODE
1
10
store setpoints
DATA STARTING ADDRESS
2
04 5C
setpoint address 04
5C
NUMBER OF SETPOINTS
2
00 02
2 setpoints
CRC
2
82 7A
CRC error code
Содержание ML Series 350
Страница 4: ......
Страница 8: ...iv 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE ...
Страница 10: ...1 2 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 1 COMMUNICATIONS INTERFACES ...
Страница 108: ...4 38 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE SR3 IEC 61850 GOOSE DETAILS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 138: ...4 68 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE IEC 61850 COMMON DATA CLASS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 148: ...5 10 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE OPC UA POINT LISTS CHAPTER 5 OPC UA COMMUNICATION STANDARD ...
Страница 152: ...6 4 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 6 USB INTERFACE ...
Страница 300: ...10 8 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS USER MAP CHAPTER 10 USING THE MODBUS USER MAP ...