CHAPTER 3: ETHERNET INTERFACE
DNP ETHERNET PROTOCOL SETTINGS
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
3–23
NOTE
NOTE:
The setting
DNP Unsolicited Response Timeout
affects DNP TCP clients only; not serial
and UDP clients. Possible values that can be selected for this setting lie between 0 and 60
seconds.
In addition to this selected timeout, up to an additional 10 seconds is required to send
the response packet.
Table 3-2: DNP point list
DNP Client Address 5
0. 0. 0. 0
F150
DNP TCP/UDP Port Number
20000
0 to 65535
F1
DNP Unsol Resp Function
Disabled
Disabled ; Enabled
F126
DNP Unsol Resp Timeout
5 s
0 to 60 s
F1
DNP Unsol Resp Max Retries
10
1 to 255
F1
DNP Unsol Resp Dest Addr
1
0 to 65519
F1
DNP Time Sync IIN Period
1440 min
1 to 10080 min
F1
DNP Message Fragment Size
240
30 to 2048
F1
DNP Object 1 Default Variation
2
1 ; 2
F1
DNP Object 2 Default Variation
2
1 ; 2
F1
DNP Object 20 Default Variation
1
1 ; 2 , 5 ; 6
F78
DNP Object 21 Default Variation
1
1 ; 2 ; 9 ; 10
F79
DNP Object 22 Default Variation
1
1 ; 2 , 5 ; 6
F80
DNP Object 23 Default Variation
1
1 ; 2 , 5 ; 6
F81
DNP Object 30 Default Variation
1
1 ; 2 ;3 ; 4
F82
DNP Object 32 Default Variation
1
1 ; 2 ;3 ; 4
F83
DNP TCP Connection Timeout
120 s
10 to 300 s
F1
SETTINGS
PARAMETER
RANGE
FORMAT
SETTINGS
PARAMETER RANGE
FORMAT
Binary Input Point 0 Entry
Select entry
from a list
Operands
F134
Binary Input Point 63 Entry
Select entry
from a list
Operands
F134
Analog Input Point 0 Entry
Select entry
from a list
Analog parameters
Analog Input Point 0 Scale Factor 1
0.001 ; 0.01 ; 0.1 ; 1 ; 10 ; 100 ;
1000 ; 10000 ; 100000
F85
Analog Input Point 0 Deadband
30000
0 to 100000000
F9
Analog Input Point 31 Entry
Select entry
from a list
Analog parameters
Analog Input Point 31 Scale
Factor
1
0.001 ; 0.01 ; 0.1 ; 1 ; 10 ; 100 ;
1000 ; 10000 ; 100000
F85
Analog Input Point 31 Deadband 30000
0 to 100000000
F9
Binary Output Point 0 ON
Select entry
from a list
Virtual Input 1 to 32 and Force
Coils
F86
Binary Output Point 0 OFF
Select entry
from a list
Virtual Input 1 to 32 and Force
Coils
F86
Содержание ML Series 350
Страница 4: ......
Страница 8: ...iv 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE ...
Страница 10: ...1 2 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 1 COMMUNICATIONS INTERFACES ...
Страница 108: ...4 38 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE SR3 IEC 61850 GOOSE DETAILS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 138: ...4 68 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE IEC 61850 COMMON DATA CLASS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 148: ...5 10 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE OPC UA POINT LISTS CHAPTER 5 OPC UA COMMUNICATION STANDARD ...
Страница 152: ...6 4 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 6 USB INTERFACE ...
Страница 300: ...10 8 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS USER MAP CHAPTER 10 USING THE MODBUS USER MAP ...