9–8
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
PERFORMING COMMANDS USING FUNCTION CODE 10H
CHAPTER 9: MODBUS FUNCTIONS
Performing Commands Using Function Code 10H
Commands can be performed using function code 16 as well as function code 5. When
using FUNCTION CODE 16, the Command Function register must be written with a value of
5. The Command Operation register must be written with a valid command operation
number. The Command Data registers must be written with valid data; this is dependent
upon the command operation.
For example, consider a request for slave 17 to perform command operation 1 (RESET): The
master/slave packets have the following format:
Table 9-9: MASTER/SLAVE PACKET FORMAT FOR PERFORMING COMMANDS
4100
Force Virtual Input 5 State
4101
Force Virtual Input 6 State
4102
Force Virtual Input 7 State
4103
Force Virtual Input 8 State
4104
Force Virtual Input 9 State
4105
Force Virtual Input 10 State
4106
Force Virtual Input 11 State
4107
Force Virtual Input 12 State
4108
Force Virtual Input 13 State
4109
Force Virtual Input 14 State
4110
Force Virtual Input 15 State
4111
Force Virtual Input 16 State
4112
Force Virtual Input 17 State
4113
Force Virtual Input 18 State
4114
Force Virtual Input 19 State
4115
Force Virtual Input 20 State
4116
Force Virtual Input 21 State
4117
Force Virtual Input 22 State
4118
Force Virtual Input 23 State
4119
Force Virtual Input 24 State
4120
Force Virtual Input 25 State
4121
Force Virtual Input 26 State
4122
Force Virtual Input 27 State
4123
Force Virtual Input 28 State
4124
Force Virtual Input 29 State
4125
Force Virtual Input 30 State
4126
Force Virtual Input 31 State
4127
Force Virtual Input 32 State
Modbus Address
Hex Address
Description
MASTER TRANSMISSION
BYTES
EXAMPLE
DESCRIPTION
SLAVE ADDRESS
1
11
message for slave 17
FUNCTION CODE
1
10
store multiple
setpoints
DATA STARTING ADDRESS
2
00 80
setpoint address 00
80
Содержание ML Series 350
Страница 4: ......
Страница 8: ...iv 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE ...
Страница 10: ...1 2 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 1 COMMUNICATIONS INTERFACES ...
Страница 108: ...4 38 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE SR3 IEC 61850 GOOSE DETAILS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 138: ...4 68 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE IEC 61850 COMMON DATA CLASS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 148: ...5 10 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE OPC UA POINT LISTS CHAPTER 5 OPC UA COMMUNICATION STANDARD ...
Страница 152: ...6 4 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 6 USB INTERFACE ...
Страница 300: ...10 8 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS USER MAP CHAPTER 10 USING THE MODBUS USER MAP ...