350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
IEC 60870-5-103 SERIAL COMMUNICATION
CHAPTER 2: RS485 INTERFACE
Application level
Application functions
The unbalanced transmission mode of the protocol is used to avoid the possibility of more
than one protection device attempting to transmit on the channel at the same time, over
the RS485 port.
Data is transferred to the primary or control station (master) using the “data acquisition by
polling” principle. Cyclically, the master will request class 2 data to the secondary station
(slave).
When slave has class 1 data (high priority) pending, the ACD control bit will be set to 1
demanding the master to request for that data.
Periodically, the master may send a General Interrogation in order to update the complete
database.
The measurands will be sent to the primary station as a response to class 2 request. A
setting (0 to 60 min) is available to configure the desired interval, where 0 means
transmission as fast as possible.
The following functions are supported:
•
Initialization
•
General Interrogation
•
Synchronization
•
Commands transmission
Type identification
The Type Identification implemented will be:
TYPE IDENTIFICATION UI8[1..8] <1..255>
<1..31>:= definitions of this companion standard(compatible range)
<32..255>:= for special use (private range)
Information in monitor direction:
<1>:= time-tagged message
<3>:= measurands I
<5>:= identification
<6>:= time synchronization
<8>:= general interrogation termination
<9>:= measurands II
Information in control direction:
<6>:= time synchronization
<7>:= general interrogation
<20>:= general command
Function type
FUNCTION TYPE UI8 [1..8] <0..255>
<0..127>:= private range
<128..129>:= compatible range
<130..143>:= private range
<144..145>:= compatible range
<146..159>:= private range
<160..161>:= compatible range
<162..175>:= private range
<176..177>:= compatible range
<178..191>:= private range
<192..193>:= compatible range
<194..207>:= private range
Содержание ML Series 350
Страница 4: ......
Страница 8: ...iv 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE ...
Страница 10: ...1 2 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 1 COMMUNICATIONS INTERFACES ...
Страница 108: ...4 38 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE SR3 IEC 61850 GOOSE DETAILS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 138: ...4 68 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE IEC 61850 COMMON DATA CLASS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 148: ...5 10 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE OPC UA POINT LISTS CHAPTER 5 OPC UA COMMUNICATION STANDARD ...
Страница 152: ...6 4 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 6 USB INTERFACE ...
Страница 300: ...10 8 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS USER MAP CHAPTER 10 USING THE MODBUS USER MAP ...