CHAPTER 3: ETHERNET INTERFACE
IEC60870-5-104 PROTOCOL
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
3–27
Table 3-4: Process information in control direction
Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
Table 3-5: System information in monitor direction
Table 3-6: System information in control direction
Table 3-7: Parameter in control direction
Table 3-8: File transfer
Number / description
Mnemonic
⊠
<45> := Single command
C_SC_NA_1
⊠
<46> := Double command
C_DC_NA_1
□
<47> := Regulating step command
C_RC_NA_1
□
<48> := Set point command, normalized value
C_SE_NA_1
□
<49> := Set point command, scaled value
C_SE_NB_1
□
<50> := Set point command, short floating point value
C_SE_NC_1
□
<51> := Bitstring of 32 bits
C_BO_NA_1
⊠
<58> := Single command with time tag CP56Time2a
C_SC_TA_1
⊠
<59> := Double command with time tag CP56Time2a
C_DC_TA_1
□
<60> := Regulating step command with time tag CP56Time2a
C_RC_TA_1
□
<61> := Set point command, normalized value with time tag CP56Time2a
C_SE_TA_1
□
<62> := Set point command, scaled value with time tag CP56Time2a
C_SE_TB_1
□
<63> := Set point command, short floating point value with time tag
CP56Time2a
C_SE_TC_1
□
<64> := Bitstring of 32 bits with time tag CP56Time2a
C_BO_TA_1
Number / description
Mnemonic
⊠
<70> := End of initialization
M_EI_NA_1
Number / description
Mnemonic
⊠
<100> := Interrogation command
C_IC_NA_1
⊠
<101> := Counter interrogation command
C_CI_NA_1
⊠
<102> := Read command
C_RD_NA_1
⊠
<103> := Clock synchronization command (see Clause 7.6 in standard)
C_CS_NA_1
⊠
<105> := Reset process command
C_RP_NA_1
⊠
<107> := Test command with time tag CP56Time2a
C_TS_TA_1
Number / description
Mnemonic
□
<110> := Parameter of measured value, normalized value
PE_ME_NA_1
⊠
<111> := Parameter of measured value, scaled value
PE_ME_NB_1
□
<112> := Parameter of measured value, short floating point value
PE_ME_NC_1
□
<113> := Parameter activation
PE_AC_NA_1
Number / description
Mnemonic
□
<120> := File ready
F_FR_NA_1
□
<121> := Section ready
F_SR_NA_1
□
<122> := Call directory, select file, call file, call section
F_SC_NA_1
□
<123> := Last section, last segment
F_LS_NA_1
□
<124> := Ack file, ack section
F_AF_NA_1
□
<125> := Segment
F_SG_NA_1
□
<126> := Directory (blank or X, available only in monitor [standard] direction) F_DR_TA_1
□
<127> := Query log - Request archive file
F_SC_NB_1
Содержание ML Series 350
Страница 4: ......
Страница 8: ...iv 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE ...
Страница 10: ...1 2 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 1 COMMUNICATIONS INTERFACES ...
Страница 108: ...4 38 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE SR3 IEC 61850 GOOSE DETAILS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 138: ...4 68 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE IEC 61850 COMMON DATA CLASS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 148: ...5 10 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE OPC UA POINT LISTS CHAPTER 5 OPC UA COMMUNICATION STANDARD ...
Страница 152: ...6 4 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 6 USB INTERFACE ...
Страница 300: ...10 8 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS USER MAP CHAPTER 10 USING THE MODBUS USER MAP ...