CHAPTER 4: SR3 IEC61850 GOOSE
SR3 GOOSE CONFIGURATION VIA THE IEC 61850 CONFIGURATOR
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
4–29
2.4.
Within the GOOSE transmission control block work area you will see the SR3xx
IED icon with IED name “one”. Click on the icon and open the directory tree until
the GOOSE ID is displayed.
2.5.
Click on the GOOSE ID to allow the GOOSE transmission properties work area to
become visible for editing.
2.6.
Enter a unique name for the GOOSE transmission. In our example we will use
the name
TX1
. Once entered, and the configuration complete, the name TX1
will be assigned to the GOOSE message transmitted from this relay. Optionally,
you can also enter a unique name for the GOOSE control block.
2.7.
The directory tree within the data set source work area can be expanded such
that digital and analog data values of different logical nodes can be accessed.
Sixty four of these data values can be dragged into the data settlements work
area to form the GOOSE message that will be transmitted.
Содержание ML Series 350
Страница 4: ......
Страница 8: ...iv 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE ...
Страница 10: ...1 2 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 1 COMMUNICATIONS INTERFACES ...
Страница 108: ...4 38 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE SR3 IEC 61850 GOOSE DETAILS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 138: ...4 68 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE IEC 61850 COMMON DATA CLASS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 148: ...5 10 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE OPC UA POINT LISTS CHAPTER 5 OPC UA COMMUNICATION STANDARD ...
Страница 152: ...6 4 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 6 USB INTERFACE ...
Страница 300: ...10 8 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS USER MAP CHAPTER 10 USING THE MODBUS USER MAP ...