CHAPTER 3: ETHERNET INTERFACE
MODBUS TCP/IP
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
3–11
Response
:
The normal response returns the slave address, function code, starting address, and
quantity of registers preset.
42H Read Settings Group
Not a standard function.
All the protection function has two sets of settings - Group 1 and Group 2. This function
number is used to read the settings for each group.
Example:
Response:
43H Write Settings Group
Not a standard function
This function is used to write settings in a specific settings group.
Example:
(In the example there is a write setting procedure in the Group 1 (00) , setting
address 0x09C1 and 2 bytes of data with value 0x0001.)
Byte Count 04
04
Data Hi
00
Data Lo
01
Data Hi
00
Data Lo
00
Field Name
Hex
Slave Address
FE
Function
10
Starting Address Hi
0F
Starting Address Lo
0A
No. of Registers Hi
00
No. of Registers Lo
02
Field Name
Hex
Slave Address
FE
Function
42
Group Activation
00
Starting Address Hi
0A
Starting Address Lo
B3
No. of Registers Hi
00
No. of Registers Lo
01
Field Name
Hex
Slave Address
FE
Function
42
Byte Count
02
Data Hi
00
Data Lo
00
Field Name
Hex
Содержание ML Series 350
Страница 4: ......
Страница 8: ...iv 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE ...
Страница 10: ...1 2 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 1 COMMUNICATIONS INTERFACES ...
Страница 108: ...4 38 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE SR3 IEC 61850 GOOSE DETAILS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 138: ...4 68 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE IEC 61850 COMMON DATA CLASS CHAPTER 4 SR3 IEC61850 GOOSE ...
Страница 148: ...5 10 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE OPC UA POINT LISTS CHAPTER 5 OPC UA COMMUNICATION STANDARD ...
Страница 152: ...6 4 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 6 USB INTERFACE ...
Страница 300: ...10 8 350 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS USER MAP CHAPTER 10 USING THE MODBUS USER MAP ...