2. OPERATION PRINCIPLES
12
DTR Digital Tap Changer Controller
GE—106305A
Failed Tap-UP:
This state shows that the tap increase operation has failed. The DTR system changes to the Manual state,
independently of the state previous to the Tap-up attempt.
11. Successful Tap-Down:
This state shows that the tap decrease operation has been successful. The DTR system returns to the initial state,
previous to the tap decrease, either Manual or Automatic.
12. Failed Tap-Down:
This state shows that the tap decrease operation has failed. The DTR system changes to the Manual state,
independently of the state previous to the Tap-down attempt.
2.1.4 EXCESSIVE OPERATIONS BLOCK.
This function allows the user to limit the number of raising/lowering tap operations over the OLTC. The user can set
this function for maintenance purposes.
When the DTR is in automatic mode, and the maximum number of allowed operations is exceeded, it will change to
Manual mode. This function can be disabled by setting the
Maximum number of operations
to zero.
2.1.5 SUCCESSIVE OPERATIONS IN A CERTAIN TIME FRAME BLOCK
This function allows the user to limit the number of raising / lowering tap operations in a specified time interval.
When the regulator is in Automatic Mode and there are continuous operations at a higher speed than the one
specified by
Number of Successive Operations
and
Time window
settings, the DTR will change to Manual mode.
Once this function is enabled, it will disable itself after a certain time without operations over the OLTC.
This function can be disabled by setting the
Number of Successive Operations
to zero.
2.1.6 OVERVOLTAGE, UNDERVOLTAGE AND OVERCURRENT BLOCKS.
When the DTR is in automatic mode, before performing any operation over the OLTC, it checks that the voltage
levels are within the limits specified by
Overvoltage
and
Undervoltage
settings. It also checks that the measured
current is lower than
Overcurrent
setting. In order to enable control over different operations when in MANUAL
mode independently from the protection element blocks, the relay incorporates three settings: BLOQ. M. OVER_V,
BLOQ. M. UNDER_V y BLOQ. M. OVER_I, which allow to consider or not the block condition.
2.1.7 QUICK LOWERING FUNCTION
If
the measured voltage exceeds the value set for Quick Lowering,
Then
the Operating Time becomes 0 s, and
therefore the lowering tap operation is instantaneous.
Содержание DTR GEK-106305A
Страница 5: ...TABLE OF CONTENTS 4 DTR Digital Tap Changer Controller GE 106305A ...
Страница 49: ...4 PROGRAMMING THE UNIT 48 DTR Digital Tap Changer Controller GE 106305A ...
Страница 55: ...5 TECHNICAL CHARACTERISTICS 54 DTR Digital Tap Changer Controller GE 106305A ...
Страница 71: ...8 INSTALLATION AND MAINTENANCE 70 DTR Digital Tap Changer Controller GE 106305A ...
Страница 83: ...9 KEYPAD AND DISPLAY 82 DTR Digital Tap Changer Controller GE 106305A ...
Страница 87: ...FIGURES 86 DTR Digital Tap Changer Controller GE 106305A FIGURE 3 PANEL MOUNTING DIAGRAM ...
Страница 88: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 87 FIGURE 4 RS 232 CONNECTION ...
Страница 89: ...FIGURES 88 DTR Digital Tap Changer Controller GE 106305A FIGURE 5 DIMENSIONS DIAGRAM ...
Страница 90: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 89 FIGURE 6 FRONT VIEW ...
Страница 91: ...FIGURES 90 DTR Digital Tap Changer Controller GE 106305A FIGURE 8 GENERIC REAR VIEW ...