4. PROGRAMMING THE UNIT
42
DTR Digital Tap Changer Controller
GE—106305A
CONFIGURABLE INPUTS
Tap 12
Tap 13
Tap 14
Tap 15
Tap 16
Tap 17
Tap 18
Tap 19
Tap 20
Tap 21
Tap 22
Tap 23
Tap 24
Tap 25
Tap 26
Tap 27
Tap 28
Tap 29
Tap 30
Additionally to these possibilities, we can use programmable inputs for creating logic schemes using logic
AND/OR/NOT gates with the inputs, and assigning them to outputs. For creating these schemes, we must program
inputs as “Void input”.
The following lines detail the operation of each input:
•
Selection table 1
: This input is activated by level, and it’s used for switching the active settings table. Please
refer to section 2.5 for further details.
•
Selection table 2
: As in the previous case.
•
Interlocking 1:
Used for blocking the operation of the regulation automatism (in automatic mode).
•
Interlocking 2:
Used for blocking the operation of the regulation automatism (in automatic mode).
•
Regulator Alarm:
Signals the activation of the Alarm input in the commuter
•
BCD_1
to
BCD_6:
Used for informing the unit, using BCD (Binary Coded Decimal) coding, of the tap where the
OLTC is located.
•
Tap-up:
This input commands a tap increase.
•
Tap-down:
This input commands a tap decrease.
•
Automatic:
Command for switching to the Automatic operation mode.
•
Manual:
Command for switching to the Manual operation mode.
•
Remote:
Command for switching to the Remote operation mode.
•
Local:
Command for switching to the Local operation mode.
•
Stopped:
Command for stopping the regulation automatism.
Содержание DTR GEK-106305A
Страница 5: ...TABLE OF CONTENTS 4 DTR Digital Tap Changer Controller GE 106305A ...
Страница 49: ...4 PROGRAMMING THE UNIT 48 DTR Digital Tap Changer Controller GE 106305A ...
Страница 55: ...5 TECHNICAL CHARACTERISTICS 54 DTR Digital Tap Changer Controller GE 106305A ...
Страница 71: ...8 INSTALLATION AND MAINTENANCE 70 DTR Digital Tap Changer Controller GE 106305A ...
Страница 83: ...9 KEYPAD AND DISPLAY 82 DTR Digital Tap Changer Controller GE 106305A ...
Страница 87: ...FIGURES 86 DTR Digital Tap Changer Controller GE 106305A FIGURE 3 PANEL MOUNTING DIAGRAM ...
Страница 88: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 87 FIGURE 4 RS 232 CONNECTION ...
Страница 89: ...FIGURES 88 DTR Digital Tap Changer Controller GE 106305A FIGURE 5 DIMENSIONS DIAGRAM ...
Страница 90: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 89 FIGURE 6 FRONT VIEW ...
Страница 91: ...FIGURES 90 DTR Digital Tap Changer Controller GE 106305A FIGURE 8 GENERIC REAR VIEW ...