3. SETTINGS
GEK-106305A
DTR Digital Tap Changer Controller
37
3.2 COMMENTS ABOUT THE SETTINGS
3.2.1 GENERAL SETTINGS
1.1 RELAY
STATUS:
This setting allows putting the system out or in service. If out of service, the system will never close any output,
except the equipment alarm output, that will be continuously closed until the system is set to be in service. While out
of service, the READY LED on the frontal plate will be red.
1.2 IDENTIFICATION:
This setting lets the user to introduce a name for the unit in order to identify the system with a maximum of 20 ASCII
characters. As this is an alphanumeric setting, it cannot be changed from the local numeric keypad (HMI) on the
frontal plate of the system.
1.3 FREQUENCY:
This setting corresponds to the frequency of the power system: 50 or 60 Hertz’s
1.4 VT
RATIO:
This setting allows the user to visualize the measured voltages on primary values. It does not apply to measures for
events and oscillography records, since these are always secondary values.
1.5 CT
RATIO:
This setting allows the user to visualize the measured currents on primary values. It does not apply to measures for
events and oscillography records, since these are always secondary values.
1.6 ACTIVE
TABLE:
This setting lets the user to select which of the three settings tables of the DTR unit is active at a given moment. This
selection can also be carried out by means of digital inputs configured for this purpose. If there is a disagreement
between this setting and the input selection, the last one has priority over the table selection via setting.
1.7 ALGORITHM:
This setting allows the user to select the regulation algorithm that DTR unit must apply:
1
Comparing the measured voltage with the setpoint
2
Compensating the voltage dropouts produced by the load current
1.8 RATED
VOLTAGE:
It is necessary to set the nominal voltage (phase to phase) on secondary value, because regulation values are set in
% of this nominal voltage.
Содержание DTR GEK-106305A
Страница 5: ...TABLE OF CONTENTS 4 DTR Digital Tap Changer Controller GE 106305A ...
Страница 49: ...4 PROGRAMMING THE UNIT 48 DTR Digital Tap Changer Controller GE 106305A ...
Страница 55: ...5 TECHNICAL CHARACTERISTICS 54 DTR Digital Tap Changer Controller GE 106305A ...
Страница 71: ...8 INSTALLATION AND MAINTENANCE 70 DTR Digital Tap Changer Controller GE 106305A ...
Страница 83: ...9 KEYPAD AND DISPLAY 82 DTR Digital Tap Changer Controller GE 106305A ...
Страница 87: ...FIGURES 86 DTR Digital Tap Changer Controller GE 106305A FIGURE 3 PANEL MOUNTING DIAGRAM ...
Страница 88: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 87 FIGURE 4 RS 232 CONNECTION ...
Страница 89: ...FIGURES 88 DTR Digital Tap Changer Controller GE 106305A FIGURE 5 DIMENSIONS DIAGRAM ...
Страница 90: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 89 FIGURE 6 FRONT VIEW ...
Страница 91: ...FIGURES 90 DTR Digital Tap Changer Controller GE 106305A FIGURE 8 GENERIC REAR VIEW ...