7. ACCEPTANCE TESTS
66
DTR Digital Tap Changer Controller
GE—106305A
7.8.4 VERIFICATION OF UNDERVOLTAGE, OVERVOLTAGE, AND OVERCURRENT CONTACTS
Remove voltage from terminals A7-A8
•
Verify that S10 is active
•
Apply 135 V between A7-A8 and check that S10 deactivates, and S11 activates
•
Set the rated current to 1 A and apply 5 A between terminals B3-B4. Check that S12 activates
•
Set the rated current to 5 A and apply 8 A between terminals A1-A2. Check that S12 activates
7.9 DYNAMIC VERIFICATION OF THE REGULATOR OPERATION
For an adequate and easy testing, we strongly recommend to wire, at least, the inputs associated to the first six taps
towards breakers, and apply voltage to inputs through them.
It is required to follow the sequence in the shown order.
These instructions assume that the tap status information is sent to the relay in BCD format.
INPUT
FUNCTION
E1
TAP BCD1
E2
TAP BCD 2
E3
TAP BCD 3
E4
TAP BCD 4
E5
TAP BCD 5
E6
TAP BCD 6
Содержание DTR GEK-106305A
Страница 5: ...TABLE OF CONTENTS 4 DTR Digital Tap Changer Controller GE 106305A ...
Страница 49: ...4 PROGRAMMING THE UNIT 48 DTR Digital Tap Changer Controller GE 106305A ...
Страница 55: ...5 TECHNICAL CHARACTERISTICS 54 DTR Digital Tap Changer Controller GE 106305A ...
Страница 71: ...8 INSTALLATION AND MAINTENANCE 70 DTR Digital Tap Changer Controller GE 106305A ...
Страница 83: ...9 KEYPAD AND DISPLAY 82 DTR Digital Tap Changer Controller GE 106305A ...
Страница 87: ...FIGURES 86 DTR Digital Tap Changer Controller GE 106305A FIGURE 3 PANEL MOUNTING DIAGRAM ...
Страница 88: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 87 FIGURE 4 RS 232 CONNECTION ...
Страница 89: ...FIGURES 88 DTR Digital Tap Changer Controller GE 106305A FIGURE 5 DIMENSIONS DIAGRAM ...
Страница 90: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 89 FIGURE 6 FRONT VIEW ...
Страница 91: ...FIGURES 90 DTR Digital Tap Changer Controller GE 106305A FIGURE 8 GENERIC REAR VIEW ...