2. OPERATION PRINCIPLES
24
DTR Digital Tap Changer Controller
GE—106305A
2.4.2 SIGNALING
In addition to the above described alarms, DTR system allows the user to define another type of events called
Signalings.
The difference between alarms and signalings is that signalings are not shown on the local graphical MMI on the
front of the relay, and they do not require the treatment described for the alarms (acknowledgement, deletion, etc.).
The configured signalings will be sent to upper levels (Level 2 and Level 3) by the communication link as soon as
they are generated. They can also be sent to a local printer if available.
2.4.3 COMMANDS
The DTR system allows the user to perform the following operations.
•
SET DATE/TIME.
•
COMMUNICATION TRIGGER
•
STOP REGULATION AUTOMATISM
•
AUTOMATISM IN AUTOMATIC MODE
•
AUTOMATISM IN MANUAL MODE.
•
RAISE THE TAP
•
LOWER THE TAP
•
REMOTE TRIP COMMAND
These operations can be carried out by means of local communications (HMI or communication software), by remote
communications or by pulse inputs (conventional RTU).
2.4.4 TIME SYNCHRONIZATION
The DTR system includes an input for time synchronization. This input requires the connection of a device to supply
a demodulated IRIG-B output. In this way, co-ordinated universal time is measured to a high degree of accuracy and
this makes it possible to tag the events generated by the unit with a resolution of one millisecond.
The use of this input makes it possible to correlate data obtained from different units thanks to synchronization with
GPS satellites. This way, it is possible to obtain very useful information for analysis, cross-referencing the information
provided by different units for a given incident.
Alternatively, it is possible to synchronize units by means of communications, using the GE_LOCAL communications
software, or manually by means of the HMI. If the IRIG_B input is used, it has priority over time setting by
communications, since the time read by IRIG_B is much more accurate.
Содержание DTR GEK-106305A
Страница 5: ...TABLE OF CONTENTS 4 DTR Digital Tap Changer Controller GE 106305A ...
Страница 49: ...4 PROGRAMMING THE UNIT 48 DTR Digital Tap Changer Controller GE 106305A ...
Страница 55: ...5 TECHNICAL CHARACTERISTICS 54 DTR Digital Tap Changer Controller GE 106305A ...
Страница 71: ...8 INSTALLATION AND MAINTENANCE 70 DTR Digital Tap Changer Controller GE 106305A ...
Страница 83: ...9 KEYPAD AND DISPLAY 82 DTR Digital Tap Changer Controller GE 106305A ...
Страница 87: ...FIGURES 86 DTR Digital Tap Changer Controller GE 106305A FIGURE 3 PANEL MOUNTING DIAGRAM ...
Страница 88: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 87 FIGURE 4 RS 232 CONNECTION ...
Страница 89: ...FIGURES 88 DTR Digital Tap Changer Controller GE 106305A FIGURE 5 DIMENSIONS DIAGRAM ...
Страница 90: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 89 FIGURE 6 FRONT VIEW ...
Страница 91: ...FIGURES 90 DTR Digital Tap Changer Controller GE 106305A FIGURE 8 GENERIC REAR VIEW ...