2. OPERATION PRINCIPLES
18
DTR Digital Tap Changer Controller
GE—106305A
PARALLEL EEPROM ALARM
This signal becomes active when the system detects an error on the non-volatile RAM (Parallel EEPROM) where
event list and counters are stored.
SERIAL EEPROM ALARM
This signal becomes active when the system detects an error on the non-volatile RAM (Serial EEPROM), where
a duplicate of the unit settings are stored (duplicated).
DEFAULT GENERAL SETTINGS
If the General Settings have never been changed, the system has the factory default General Settings. This signal
shows this situation.
TABLE 1 DEFAULT SETTINGS
If the settings on Table 1 have never been changed, the system has the factory default Table 1 settings. This
signal shows this situation.
TABLE 2 DEFAULT SETTINGS
If the settings on Table 2 have never been changed, the system has the factory default Table 2 settings. This
signal shows this situation.
TABLE 3 DEFAULT SETTINGS
If the settings on Table 3 have never been changed, the system has the factory default Table 3 settings. This
signal shows this situation.
EXTERNAL TRIGGER
This signal turns ON and OFF as the External Trigger Digital Input is energized and de-energized.
TABLE 1 ACTIVE
TABLE 2 ACTIVE
TABLE 3 ACTIVE
These three signals report which table is active each time. If the digital inputs intended to change tables are de-
energized, then these signals would reflect the value set on setting ACTIVE TABLE.
COMMUNICATIONS TRIGGER
This signal becomes active when a trigger command is issued, either from the local HMI (keyboard and display on
the front of the relay) or from the GE_LOCAL communications software.
STOPPED
This signal becomes active when the regulation automatism is stopped.
Содержание DTR GEK-106305A
Страница 5: ...TABLE OF CONTENTS 4 DTR Digital Tap Changer Controller GE 106305A ...
Страница 49: ...4 PROGRAMMING THE UNIT 48 DTR Digital Tap Changer Controller GE 106305A ...
Страница 55: ...5 TECHNICAL CHARACTERISTICS 54 DTR Digital Tap Changer Controller GE 106305A ...
Страница 71: ...8 INSTALLATION AND MAINTENANCE 70 DTR Digital Tap Changer Controller GE 106305A ...
Страница 83: ...9 KEYPAD AND DISPLAY 82 DTR Digital Tap Changer Controller GE 106305A ...
Страница 87: ...FIGURES 86 DTR Digital Tap Changer Controller GE 106305A FIGURE 3 PANEL MOUNTING DIAGRAM ...
Страница 88: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 87 FIGURE 4 RS 232 CONNECTION ...
Страница 89: ...FIGURES 88 DTR Digital Tap Changer Controller GE 106305A FIGURE 5 DIMENSIONS DIAGRAM ...
Страница 90: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 89 FIGURE 6 FRONT VIEW ...
Страница 91: ...FIGURES 90 DTR Digital Tap Changer Controller GE 106305A FIGURE 8 GENERIC REAR VIEW ...