Chapter 1. Programming Site Data
30
DigitalFlow™ GF868 Programming Manual (2-Channel)
1.7.3 Setting Up Global Inputs/Outputs (cont.)
Option Card RTD Inputs
Option cards with RTD inputs have a temperature range of –100 ° to 350 °C. Complete the following steps to set up the
two RTD inputs of an option card installed in Slot x:
1.
Press
[F1]
to set up RTD input A or
[F2]
to set up RTD input B.
Note:
The setup of RTD input A is used as an example. Identical procedures would be used to set up RTD input B.
2.
Enter a label of up to eight characters and press
[ENT]
.
3.
At the
Input Measurement
prompt, press
[F1] = OFF
to disable RTD input A and return to the previous prompt, or
press
[F2] = TEMP
to enable RTD input A.
4.
Enter the
Zero Value
for the low end of the chosen input range and press
[ENT]
.
5.
Enter the
Full Scale Value
for the high end of the chosen input range and press
[ENT]
.
6.
Press
[F1]
-
[F2]
to set up another input or press
[EXIT]
to select another slot for set up.
For instructions on setting up additional inputs and/or outputs, proceed to the appropriate section. Otherwise, press
[EXIT]
twice to return to the
Global PROGRAM
prompt.
Procedure Options
After completing the above steps, the meter returns to the
Global I/O
prompt. Continue as follows:
•
To continue programming the meter, refer to the menu maps in Appendix A and navigate to the desired menu.
Then, proceed to the appropriate section of this manual for instructions.
•
To leave the User Program and retain the previous settings, press
[EXIT]
twice and then press
[F1] = NO
at the
SAVE
prompt. Any programming changes will be discarded and you will be returned to the data display.
•
To leave the
User Program
and return to measurement mode, press
[EXIT]
twice and then press
[F2] = YES
at the
SAVE
prompt. Your programming changes will be entered into the meter’s memory, and you will be returned to
the data display.
Note:
See the
SAVE
submenu section on page 37 of this chapter for more information on this function.
Содержание DigitalFlow GF868
Страница 2: ......
Страница 4: ...ii no content intended for this page ...
Страница 10: ...Contents viii DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Страница 60: ...Chapter 2 Displaying Data 50 DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Страница 95: ...DigitalFlow GF868 Programming Manual 2 Channel 85 Appendix A Menu Maps Appendix A Menu Maps ...
Страница 96: ...86 DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Страница 104: ...Appendix A Menu Maps DigitalFlow GF868 Programming Manual 2 Channel 94 ...
Страница 108: ...98 DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Страница 146: ...Warranty 136 DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Страница 150: ......
Страница 151: ......