DigitalFlow™ GF868 Programming Manual (2-Channel)
29
Chapter 1. Programming Site Data
Totalizer Output
5.
The
TTLZR
output,
[F3],
issues one pulse per selected volume of flow. The meter produces a pulse each time the
programmed amount of flow passes through the pipe. Complete the steps below to program the totalizer output.
a.
Press
[F1]
= +TOTL
to totalize the forward flow,
[F2]
= -TOTL
to totalize the reverse flow,
[F3] = +MASS
(if
available) to totalize the forward mass flow or
[F4] = -MASS
(if available) to totalize reverse mass flow.
b.
Enter a value from 50 to 500,000
sec for the
Minimum Pulse
ON
Time
and press
[ENT]
.
Note:
A complete pulse consists of equal amounts of
ON
and
OFF
times. Choose a value that is compatible with the
frequency counter to be used.
c.
Enter a value for the number of measurement
Units/Pulse
and press
[ENT]
.
6.
Press
[F1]
-
[F4]
to set up another totalizer/frequency output or press
[EXIT]
to select another slot for setup.
Analog Inputs
1.
Press
[F1]
to set up input A or
[F2]
to set up input B.
Note:
The set up of input A is used as an example in this manual. Identical procedures would be used to set up input
B. (An analog input option card may contain one standard analog input and one RTD analog input.)
2.
Enter a
Label
of up to eight characters for input A and press
[ENT]
.
3.
At the
Input Measurement
prompt, press
[F1] = OFF
to disable input A and return to the previous prompt, or press
[F2] = PRESR (pressure), [F3]= TEMP (temperature) or [F4]
= SPEC
(special)
to designate the input.
4.
Do one of the following:
•
If you selected
PRESR
or
TEMP,
proceed to step 5.
•
If you selected
SPEC
, complete the steps below.
a.
Enter an
Input Name
and press
[ENT]
.
b.
Enter the
Input Units
of measurement and press
[ENT]
.
5.
Enter the
Zero Value
for the low end of the chosen input range and press
[ENT]
.
6.
Enter the
Full Scale Value
for the high end of the chosen input range and press
[ENT]
.
7.
Press
[F1]
-
[F2]
to set up another input or press
[EXIT]
to select another slot for setup.
Содержание DigitalFlow GF868
Страница 2: ......
Страница 4: ...ii no content intended for this page ...
Страница 10: ...Contents viii DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Страница 60: ...Chapter 2 Displaying Data 50 DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Страница 95: ...DigitalFlow GF868 Programming Manual 2 Channel 85 Appendix A Menu Maps Appendix A Menu Maps ...
Страница 96: ...86 DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Страница 104: ...Appendix A Menu Maps DigitalFlow GF868 Programming Manual 2 Channel 94 ...
Страница 108: ...98 DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Страница 146: ...Warranty 136 DigitalFlow GF868 Programming Manual 2 Channel no content intended for this page ...
Страница 150: ......
Страница 151: ......