9-6
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
DISTANCE ELEMENTS
CHAPTER 9: THEORY OF OPERATION
9
•
A ground element — I_0
×
Z
D
and –V_0
•
B ground element — I_0
×
Z
D
and –V_0
•
C ground element — I_0
×
Z
D
and –V_0
The limit angle of the comparator is not adjustable and equals 90°. The zero-sequence directional characteristic improves
directional integrity for time-delayed operations after the memory expires.
9.1.3.12 Overcurrent supervision
The overcurrent supervision responds to the following currents:
•
AB phase element — (I
A
– I
B
) /
•
BC phase element — (I
B
– I
C
) /
•
CA phase element — (I
C
– I
A
) /
•
A, B, C ground element — | 3
×
I_0 – 0.05
×
I_1 |
The following tables summarize the characteristics of the distance elements.
Table 9-1: Directional mho phase distance functions
Table 9-2: Directional mho ground distance functions
Table 9-3: Directional quadrilateral phase distance functions
Table 9-4: Directional quadrilateral ground distance functions
Characteristic
Comparator inputs
Limit angle
Variable mho
I
×
Z – V
V_1M
COMP LIMIT
Reactance
I
×
Z – V
I
×
Z
COMP LIMIT
Directional
I
×
ZD
V_1M
DIR COMP LIMIT
Fault type
NOT SLG
See the Fault Type Characteristic section
Removed during open pole conditions
Characteristic
Comparator inputs
Limit angle
Variable mho
I
×
Z – V
V_1M
COMP LIMIT
Reactance
I
×
Z – V
I_0
×
Z
COMP LIMIT
Directional
I_0
×
Z
D
V_1M
DIR COMP LIMIT
Directional
I_2
×
Z
D
V_1M
DIR COMP LIMIT
Fault-type
I_0
I_2
50°
Zero-sequence
I_0
×
Z
D
–V_0
90°
Characteristic
Comparator inputs
Limit angle
Reactance
I
×
Z – V
I
×
Z
COMP LIMIT
Directional
I
×
Z
D
V_1M
DIR COMP LIMIT
Right Blinder
I
×
Z
R
– V
I
×
Z
R
90°
Left Blinder
I
×
Z
L
– V
I
×
Z
L
90°
Fault type
NOT SLG
See the Fault Type Characteristic section
Removed during open pole conditions
Characteristic
Comparator inputs
Limit angle
Reactance
I
×
Z – V
j
×
I_0
×
e
j
Θ
or j
×
I_2
×
e
j
Θ
COMP LIMIT
Directional
I_0
×
Z
D
V_1M
DIR COMP LIMIT
Directional
I_2
×
Z
D
V_1M
DIR COMP LIMIT
Right Blinder
I
×
Z
R
– V
I
×
Z
R
90°
Left Blinder
I
×
Z
L
– V
I
×
Z
L
90°
Fault-type
I_0
I_2
50°
Zero-sequence
I_0
×
Z
D
–V_0
90°
Содержание D30 series
Страница 10: ...x D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 52: ...2 38 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 534: ...5 324 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 564: ...6 30 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 578: ...7 14 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 614: ...9 26 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 654: ...A 10 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 662: ...C 6 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 670: ...iv D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 686: ...xvi D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...