D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
DISTANCE ELEMENTS
CHAPTER 9: THEORY OF OPERATION
9
The relay provides for an adaptive distance reach control to cope with the overreaching and sub-synchronous oscillations
when applied to, or in a near vicinity of series compensated lines. The Application on Series Compensated Lines section
has information.
The distance elements use phase angle comparators to shape their characteristics as described in the Distance
Characteristics section. The voltage and current phasors are estimated using optimized techniques as explained in the
next section.
9.1.2 Phasor estimation
The relay samples its input AC signals at 64 samples per power system cycle. A fast and accurate frequency tracking
mechanism ensures accurate filtering and phasor estimation during off-nominal frequency conditions.
The phasor estimation process for both currents and voltages is based on the commonly used Fourier algorithm. Due to a
different nature of signal distortions in the current and voltage signals digital pre-filtering algorithms have been, however,
designed and optimized separately for the current and voltage channels.
The current signals are pre-filtered using an improved digital MIMIC filter. The filter removes effectively the DC
component(s) guaranteeing transient overshoot below 2% regardless of the initial magnitude and time constant of the DC
component(s). The filter has significantly better frequency response for higher frequencies as compared with a classical
MIMIC filter. This was possible without introducing any significant phase delay thanks to the high sampling rate used by
the relay.
The voltage signals are pre-filtered using a special digital filter designed to cope with CVT transients. The patented filter
combines filtering and memory actions enabling the relay to cope with CVT noise under high Source Impedance Ratios
(SIRs). The filter controls underestimation of the fault voltage magnitude to less than 1% of the nominal and prevents
certain phase angle anomalies that can be encountered under heavy CVT noise and high SIRs.
9.1.3 Distance characteristics
9.1.3.1 Definitions
The relay shapes its distance characteristics using phase angle comparators and voltage and current phasors estimated
as described in the previous section.
The following definitions pertain to all of the distance functions:
•
I
A
, I
B
, I
C
— Phase A, B, and C current phasors
•
I
G
— Ground current from a parallel line
•
V
A
, V
B
, V
C
— Phase A to ground, phase B to ground, and phase C to ground voltage phasors
•
( )_1 — Positive-sequence phasor of ( ) derived from the phase quantities
•
( )_2 — Negative-sequence phasor of ( ) derived from the phase quantities
•
( )_0 — Zero-sequence phasor of ( ) derived from the phase quantities
•
( )M — Memorized value of ( )
•
Z — Reach impedance (
REACH
∠
RCA
)
•
Z
REV
— Reverse reach impedance for non-directional applications (
REV REACH
∠
REV REACH RCA
+ 180°)
•
Z
D
— Directional characteristic impedance (1
∠
DIR RCA
)
•
Z
R
— Right blinder characteristic impedance: Z
R
=
RGT BLD
×
sin (
RGT BLD RCA
)
×
1
∠
(
RGT BLD RCA
– 90°)
•
Z
L
— Left blinder characteristic impedance: Z
L
=
LFT BLD
×
sin (
LFT BLD RCA
)
×
1
∠
(
LFT BLD RCA
+ 90°)
•
K0 — Zero-sequence compensating factor: K0 = (
Z0/Z1 MAG
∠
Z0/Z1 ANG
) – 1
•
K0M — Mutual zero-sequence compensating factor: K0M = 1/3 x
Z0M/Z1 MAG
∠
Z0m/Z1 ANG
•
Θ
— Non-homogeneity angle setting (
NON-HOMOGEN ANG
)
9.1.3.2 Directional mho characteristic
The dynamic 100% memory polarized mho characteristic is achieved by checking the angle between
Содержание D30 series
Страница 10: ...x D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 52: ...2 38 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 534: ...5 324 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 564: ...6 30 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 578: ...7 14 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 614: ...9 26 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 654: ...A 10 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 662: ...C 6 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 670: ...iv D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 686: ...xvi D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...