D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
The power swing detect element provides both power swing blocking and out-of-step tripping functions. The element
measures the positive-sequence apparent impedance and traces its locus with respect to either two or three user-
selectable operating characteristic boundaries. Upon detecting appropriate timing relations, the blocking and/or tripping
indications are given through FlexLogic operands. The element incorporates an adaptive disturbance detector. This
POWER SWING QUAD REV
REACH MID: 60.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING QUAD REV
REACH OUT: 70.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING REV
RCA: 75°
Range: 40 to 90° in steps of 1
POWER SWING OUTER
LIMIT ANGLE: 120°
Range: 40 to 140° in steps of 1
POWER SWING MIDDLE
LIMIT ANGLE: 90°
Range: 40 to 140° in steps of 1
POWER SWING INNER
LIMIT ANGLE: 60°
Range: 40 to 140° in steps of 1
POWER SWING OUTER
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING OUTER
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING MIDDLE
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING MIDDLE
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING INNER
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING INNER
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING PICKUP
DELAY 1: 0.030 s
Range: 0.000 to 65.535 s in steps of 0.001
POWER SWING RESET
DELAY 1: 0.050 s
Range: 0.000 to 65.535 s in steps of 0.001
POWER SWING PICKUP
DELAY 2: 0.017 s
Range: 0.000 to 65.535 s in steps of 0.001
POWER SWING PICKUP
DELAY 3: 0.009 s
Range: 0.000 to 65.535 s in steps of 0.001
POWER SWING PICKUP
DELAY 4: 0.017 s
Range: 0.000 to 65.535 s in steps of 0.001
POWER SWING SEAL-IN
DELAY: 0.400 s
Range: 0.000 to 65.535 s in steps of 0.001
POWER SWING TRIP
MODE: Delayed
Range: Early, Delayed
POWER SWING BLK:
Off
Range: FlexLogic operand
POWER SWING
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
POWER SWING
EVENTS: Disabled
Range: Disabled, Enabled
Содержание D30 series
Страница 10: ...x D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 52: ...2 38 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 534: ...5 324 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 564: ...6 30 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 578: ...7 14 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 614: ...9 26 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 654: ...A 10 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 662: ...C 6 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 670: ...iv D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 686: ...xvi D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...