CHAPTER 5: SETTINGS
SYSTEM SETUP
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
5-147
5
The breaker control element contains the auxiliary logic for status and serves as the interface for opening and closing of a
circuit breaker from protection, autoreclose, SCADA, or through the front panel interface. The breaker control element can
be used to create interlocking functionality. For greater security in determination of the breaker position, both the 52/a and
52/b auxiliary contacts are used with reporting of the discrepancy between them.
To use this element, configure the contact outputs that trip and close the breaker to use FlexLogic operands
BREAKER 1 OFF
CMD
(or
BREAKER 1 TRIP A/B/C
in the case of single-pole tripping) and
BREAKER 1 ON CMD
, and configure the breaker control
element inputs as described here.
BREAKER 1 AR BLOCK:
Disabled
Range: Disabled, Enabled
BREAKER 1 NAME:
Bkr 1
Range: up to six alphanumeric characters
BREAKER 1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
BREAKER 1 OPEN:
Off
Range: FlexLogic operand
BREAKER 1 BLK OPEN:
Off
Range: FlexLogic operand
BREAKER 1 CLOSE:
Off
Range: FlexLogic operand
BREAKER 1 BLK CLOSE:
Off
Range: FlexLogic operand
BREAKER1
Φ
A/3P CLSD:
Off
Range: FlexLogic operand
BREAKER1
Φ
A/3P OPND:
Off
Range: FlexLogic operand
BREAKER 1
Φ
B CLOSED:
Off
Range: FlexLogic operand
BREAKER 1
Φ
B OPENED:
Off
Range: FlexLogic operand
BREAKER 1
Φ
C CLOSED:
Off
Range: FlexLogic operand
BREAKER 1
Φ
C OPENED:
Off
Range: FlexLogic operand
BREAKER 1 TOPERATE:
70 ms
Range: 0 to 65535 s in steps of 1
BREAKER 1 EXT ALARM:
Off
Range: FlexLogic operand
BREAKER 1 ALARM
DELAY: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
MANUAL CLOSE RECAL1
TIME: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
BREAKER 1 OPEN
SEAL-IN: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
BREAKER 1 OUT OF SV:
Off
Range: FlexLogic operand
BREAKER 1 RACKED-IN:
Off
Range: FlexLogic operand
BREAKER 1 EVENTS:
Disabled
Range: Disabled, Enabled
Содержание D30 series
Страница 10: ...x D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 52: ...2 38 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 534: ...5 324 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 564: ...6 30 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 578: ...7 14 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 614: ...9 26 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 654: ...A 10 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 662: ...C 6 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 670: ...iv D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 686: ...xvi D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...