CHAPTER 5: SETTINGS
PRODUCT SETUP
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
5-125
5
User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The
number depends on the front panel ordered.
•
Enhanced horizontal front panel — 16 user-programmable pushbuttons
•
Enhanced vertical front panel — 6 user-programmable pushbuttons
•
Standard horizontal front panel — 12 user-programmable pushbuttons
•
Graphical front panel — 16 user-programmable pushbuttons (eight physical pushbuttons, eight graphical interface
pushbuttons)
The digital state can be entered locally (by directly pressing the front panel pushbutton or optional graphical front panel
interface) or remotely (via FlexLogic operands) into FlexLogic equations, protection elements, and control elements. Typical
applications include breaker control, autorecloser blocking, and setting groups changes. For example, set pushbuttons 1 to
5 to select settings groups 1 to 5, or set pushbutton 1 to clear event records. The user-programmable pushbuttons are
under the control level of password protection.
Example
To clear event records using pushbutton 1, set
Settings > Product Setup > Clear Relay Records > Clear Event Records
to
FlexLogic operand
PUSHBUTTON 1 ON
. Then program the pushbutton by setting
Settings > Product Setup > User-
Programmable Pushbuttons > Pushbutton 1 Function
to "Self-reset." For a graphical front panel, to use a side
pushbutton 9 to 16 to clear the event records, it also needs to be programmed in a single-line diagram.
The figures show user-configurable pushbuttons for the front panels.
Figure 5-54: User-programmable pushbuttons (enhanced front panel)
Figure 5-55: User-programmable pushbuttons (standard front panel)
The D30 is provided with this optional feature, specified as an option at the time of ordering. Using the order
code for your device, see the order codes in chapter 2 for details.
User-programmable pushbuttons require a front panel with that option. If the front panel was ordered separately,
update the EnerVista software under
Maintenance > Change Front Panel
.
Содержание D30 series
Страница 10: ...x D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 52: ...2 38 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 534: ...5 324 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 564: ...6 30 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 578: ...7 14 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 614: ...9 26 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 654: ...A 10 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 662: ...C 6 D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 670: ...iv D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 686: ...xvi D30 LINE DISTANCE PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...