GE Energy
D20/D200
Installation and Operations Guide
General 994-0078-2.00-7
Full
119
Servicing
, continued
Fuse Locations:
D200
The D200 has one field replaceable fuses located on the Power Supply together with
a spare fuse:
Replaceable
Fuses
The following table shows the standard replaceable fuses that are used in the various
hardware options for the D200.
Fuse
PS Board
Type
Replacement
Where Used
Fuse Part
Number
520-0150
MDL 10A SLO BLO
48VDC Field Supply
940-0074
F1
520-0151
MDQ 5A 250VAC
110/250VAC Field Supply
940-0028
Note
Fuses listed in the tables above are the
standard
fuses that are factory installed,
unless otherwise specified.
Fuse ratings may differ due to:
•
Unique customer-specific configurations or requirements, or
•
Product specification changes
When changing fuses,
always
check the original fuse for value and type, and ensure
the replacement fuse you use is of that value and type. Do not assume that installed
fuse is of the correct value.
Spare Fuse
Active Fuse