CE Mark Compliance Information
Overview
Individual products of the D20 and D200 automation product family are classified
according to EU Directive 2004/108/EC as subassemblies / finished appliances
exclusively intended for an industrial assembly operation for incorporation into other
apparatus. They are not apparatus in the sense of the EMC Directive.
To achieve CE mark compliance, the end user shall be responsible for ensuring the
final system/installation conforms to all requirements of the European Union
Electromagnetic Compatibility (EMC) and Low Voltage (LV) Directives. Products
installed in secondary EMC grade protection metallic cabinets and following proper
installation practices depicted in D20/D200 User Manual should meet CE mark
requirements.
For information regarding current regulatory compliance status of your order, please
contact your local sales representative or em
Classification of
D20/D200
Products from
the EMC
Directive
Perspective
The D20 and D200 line of products are intelligent, industrial grade control devices
targeted for automation and control of electrical substations. These products are
designed as modular and scalable devices allowing the non-consumer end user to
build a system of virtually any size and complexity. The number of options and
configurations can be large; therefore, trained personnel must be involved in the
design and integration of the final system. Refer to the explanatory note below.
Due to the inherent complexity and almost limitless variations of final systems, it is
not possible for the manufacturer to guarantee compliance in the factory of
individual D20/D200 modules in a final system, with the exception of pre-assembled
RTU cabinets. Therefore, the end user shall be responsible for ensuring the final
system/installation complies with all requirements of the EMC and LV Directives.
Radiated
Emissions and
Radiated
Immunity
Considerations
The D20 and D200 products have been designed and hardened to operate in the
harsh industrial environment of electrical substations. When placed in service, the
final system must conform to the objectives of the EMC Directive. To meet RF
emissions and RF susceptibility according to CISPR 11 Class “A”, all D20 and D200
products must be installed in an EMC grade secondary metallic protective
enclosure/cabinet. Additional EMC countermeasures may have to be applied
depending on complexity and size of the system.