994-0078-2.00-7 General
106
Full
D20/D200 Software Configuration
, continued
Procedure
(continued)
Step
Action
Optional Step 1: Speed-up communications to shorten download time.
8
Type
Baud 38400
and press
ENTER
.
Note:
Speeds up to 230.4 kbps, or lower speeds may be chosen based
on ambient EMI, WESMAINT cable length, PC and
communication software limitations, etc. Refer to “Appendix
B: 68K Monitor Commands”, page 127 for supported speeds.
Result: The monitor will now be communicating at 38.4 kbps
9
Configure the terminal emulator software to communicate at the same
speed, and reconnect to the 68K monitor.
Optional Step 2: Provide feedback during download
10
If the communication software you are using
does not
have any
“progress indicator”, echo can be enabled to visually display the code
file on your monitor as it is transferred.
This option can be usually found in the communication settings or
properties of the communication program.
Note:
Enabling echo may slow transfer slightly.
Download Code File
11
Press
ENTER
to verify that communication is active.
Result: The
D20MES>
prompt will return if connection is active
12
Type
dl
and press
ENTER
to put the D20ME into the state where it is
ready to receive the downloadable code file
13
Click
Transfer | Send Text File
from menu bar
Result: A dialog box will open, prompting you to locate the
Down.shx
file that you wish to download.
14
Select the correct file, and click
Open
to start the transfer
Caution:
Do not
hit any keys on keyboard during download.
Result: The file transfer may take from less than 10 to over 30
minutes, depending on communication speed selected.
When complete, the
D20MES>
prompt will return.