Procedure:
Code Download
CCU Base
To download of a flash code file to a
CCU
type of D20ME module.
Step
Action
Code Download for CCU Base type D20ME
1
Restart the D20ME.
2
When messages appear on the monitor, press
SPACEBAR
within 5
seconds.
Result: You are prompted with the message:
“Are you sure you wish to
abort the flash boot? (y/n)”
.
3
Type
y
(or
Y
) to abort the normal startup.
4
Press
ENTER
.
Result: The login dialog appears.
5
To login: for
Login:
type
westronic
and press
ENTER
, then for
Password:
type
rd
and press
ENTER
.
Result: After a Welcome message, the
D20MES>
prompt will appear.
6
Type
sp
to suspend all processes running on the D20ME
7
Type
erase
to clear the flash. This will take several seconds.
Result: The monitor will display, before returning the
D20MES>
prompt:
Erasing FLASH memory <
\ Checking FLASH contents… \
Continued on next page