58
I N S TA L L AT I O N , O P ER AT I O N S A N D M A I N T EN A N C E M A N UA L
Warning:
Unless the proper
precautions are taken, the removal of
a shutter unit presents the hazard of
electrical shock and burn. Do not
remove the shutter unit unless the
equipment has been deenergized.
Failure to do this can result in serious
injury.
Warning:
Unless the proper
precautions are taken, the
installation of a shutter unit presents
the hazard of electrical shock and
burn. Do not install the shutter unit
unless the equipment has been de-
energized. Failure to do this can
result in serious injury.
Padlocking the cradle
The circuit breaker compartment door must be
opened to put the padlock on; however, there is no
interference with the door after the padlock has
been placed in position. Padlocks will prevent the
acceptance of breakers in the cradle. The padlock
device on the cradle will accept up to three
padlocks on both the left and right sides of the
cassette. See Figure 94.
—
94
Compartment
padlock device
—
95
Shutter padlocking
—
94
—
95
Padlocking the shutter
The shutter on each cubicle can be padlocked to
prevent access to the live primary conductors.
The breaker must be removed from the
compartment to padlock the shutter. For E2.2 and
E4.2 cradles, a minimum of 2 padlocks are required
(one for the top shutter assembly and one for the
bottom shutter assembly).
For E6.2, a minimum of 4 padlocks are required (2
for the 2 top shutter assemblies and 2 for the 2
bottom shutter assemblies). See Figure 95 for
reference on how to install a padlock on the shutter.
Removing the shutter unit
Refer to 1SDH001400R0831 for full instructions on
the removal of the shutter unit.
1. Provisions for padlocks (not shown)
Size
Type
Global ordering code
E2.2
shutter top or bottom
E2.2 FP 3p ReliaGear LV SG
1SDA114343R1
E4.2
shutter top
E4.2 FP 3p ReliaGear LV SG
1SDA114345R1
shutter bottom
E4.2 FP 3p ReliaGear LV SG
1SDA114346R1
E6.2
shutter top
E6.2 FP 3p ReliaGear LV SG
1SDA114347R1
shutter bottom
E6.2 FP 3p ReliaGear LV SG
1SDA114348R1
Table 10 - Emax 2 shutter catalog numbers
1
Installing the shutter unit
Refer to
for full instructions on
installation of shutter units. Available shutter
units are listed below in Table 10.
DANGER
WARNING
CAUTION
NOTICE
DANGER
WARNING
CAUTION
NOTICE