I N S TA L L AT I O N , O P ER AT I O N S A N D M A I N T EN A N C E M A N UA L
Circuit breakers
The SACE Emax 2 low voltage power circuit breaker
includes spring-operated, stored energy, close
and trip mechanisms for either manual or
electrical operation.
SACE Emax 2 circuit breakers form the complete
family of breakers used in ReliaGear LV SG. Each
type of breaker listed in Table 2 describes the
breaker interrupting rating which corresponds to
the 3rd digit of the breaker catalog number. These
circuit breakers, in a compartment, range from 800
to 5,000 amperes.
SACE Emax 2 circuit breakers
E2.2 Emax 2 circuit breaker
• 2,000 ampere frame size;
• Up to 100kAIC interrupting rating;
• Four high stacking; 22 inch wide sections.
E4.2 Emax 2 circuit breaker
• 2,000 ampere frame size;
• Up to 100kAIC interrupting rating;
• Four high stacking; 22 inch wide sections.
E4.2 Emax 2 circuit breaker
• 3,200 ampere frame size;
• Up to 100kAIC interrupting rating;
• Available in 22 inch wide sections.
E6.2 Emax 2 circuit breaker
• 5,000 ampere frame size;
• Up to 100kAIC interrupting rating;
• Available in 38 inch wide sections.
—
25
SACE Emax 2
circuit breaker
—
26
—
25
—
26
SACE Emax 2 circuit
breaker (shown with
draw-out rails extended)
1. Contact factory
Interrupting Rating Tiers ANSI/
UL1066 Devices, LVPCB
E2.2
E4.2
E6.2
Type
254 Vac
508 Vac 635 Vac
1/2 Withstand
800, 1200,
1600, 2000
250, 800, 1200,
1600, 2000
3200
800, 1600,
2000, 3200
3200, 4000,
5000
S-A
65
65
65
65
×
×
H-A
85
85
85
85
×
×
×
V-A
100
100
85
85
×
V-A
100
100
100
100
×
×
Table 2 - Emax 2 short time and short circuit interruption ratings