LARGE CASSETTE TECHNICAL OVERVIEW
ENGLISH
Topic Title
E-10
DIP Switch Settings
Description
Capacity
Room Card
Running Mode
Unit Type
SW1-1 SW1-2 SW1-3
SW1-4
SW1-5
SW1-6 SW1-7 SW1-8
Capacity: 24kBTU(7.1kW)
ON
ON
OFF
---
---
---
---
---
Capacity: 30kBTU(9.0kW)
OFF
OFF
ON
---
---
---
---
---
Capacity: 35kBTU(10.5kW)
ON
OFF
ON
---
---
---
---
---
Capacity: 42kBTU(12.5kW)
OFF
ON
ON
---
---
---
---
---
Capacity: 48kBTU(14.0kW_
ON
ON
ON
---
---
---
---
---
Room card invalid(default)
---
---
---
OFF
---
---
---
---
Room card valid
---
---
---
ON
---
---
---
---
Heat pump(default)
---
---
---
---
OFF
---
---
---
Cooling only
---
---
---
---
ON
---
---
---
High performance cassette
---
---
---
---
---
OFF
OFF
ON
Indoor unit Address
(Indoor unit address for one wired
controller control more than one unit)
BM3-5
BM3-6
BM3-7
BM3-8
0 (master)
OFF
OFF
OFF
OFF
1 (slave)
OFF
OFF
OFF
ON
2 (slave)
OFF
OFF
ON
OFF
3 (slave)
OFF
OFF
ON
ON
4 (slave)
OFF
ON
OFF
OFF
5 (slave)
OFF
ON
OFF
ON
6 (slave)
OFF
ON
ON
OFF
7 (slave)
OFF
ON
ON
ON
8 (slave)
ON
OFF
OFF
OFF
9 (slave)
ON
OFF
OFF
ON
10 (slave)
ON
OFF
ON
OFF
11 (slave)
ON
OFF
ON
ON
12 (slave)
ON
ON
OFF
OFF
13 (slave)
ON
ON
OFF
ON
14 (slave)
ON
ON
ON
OFF
15 (slave)
ON
ON
ON
ON
BM1 DIP Switch Settings
Wired Controller Communication Address
Содержание AB09SC2VHA
Страница 2: ...Oct 2020 Manual release Revision History ...
Страница 12: ... This page intentionally left blank ...
Страница 45: ...WALL MOUNT TECHNICAL OVERVIEW ENGLISH Topic Title C 9 Wiring Diagrams ...
Страница 68: ... This page intentionally left blank ...
Страница 78: ... This page intentionally left blank ...
Страница 104: ... This page intentionally left blank ...