OUTDOOR TECHNICAL OVERVIEW
ENGLISH
B-13
Operations
High Current Protection
The below table is the outdoor unit protection current and compressor current.
If the temperature reaches 150
O
F(66
O
C) three times in one hour, the
system will lock out. Reset by turning power off and back on.
Reduce FQY rapidly 2Hz/S
Reduce FQY rapidly 1Hz/S
Reduce FQY rapidly 1Hz/10S
Remain FQY
Reduce FQY slowly 1Hz/S
100%*I
98%*I
96%*I
96%*I
90%*I
88%*I
Remain FQY
Model
Maximum current (I)
Compressor current (CT)
ASH220NCDWA
12.5A
10A
ASH324NCDWA
13.5
14A
ASH436NCDWA
???
???
High Pressure Protection in Cooling
If there is an abnormal stop 3 times in 1 hour, the unit
will turn off. Turn off and restore power to clear error.
Reduce FQY rapidly 2Hz/S
Reduce FQY slowly 1Hz/S
Remain FQY
Raise FQY slowly 1Hz/10S
131
O
F(55
O
C)
Tc--cooling
138
O
F(59
O
C)
144
O
F(62
O
C)
147
O
F(64
O
C)
150
O
F(66
O
C)
Remain FQY
If the temperature reaches 158
O
F(70
O
C) three times in one hour,
the system will lock out. Reset by turning power off and back on.
Reduce FQY rapidly 2Hz/S
Reduce FQY slowly 1Hz/S
Remain FQY
Raise FQY slowly 1Hz/10S
129
O
F(54
O
C)
Tc--heating
135
O
F(57
O
C)
138
O
F(59
O
C)
145
O
F(63
O
C)
158
O
F(70
O
C)
Remain FQY
High Pressure Protection In Heating
Содержание AB09SC2VHA
Страница 2: ...Oct 2020 Manual release Revision History ...
Страница 12: ... This page intentionally left blank ...
Страница 45: ...WALL MOUNT TECHNICAL OVERVIEW ENGLISH Topic Title C 9 Wiring Diagrams ...
Страница 68: ... This page intentionally left blank ...
Страница 78: ... This page intentionally left blank ...
Страница 104: ... This page intentionally left blank ...