TROUBLESHOOTING & REFERENCES
I-4
ENGLISH
Special Functions
Temperature Compensation
This function allows you the capability to adjust the temperature compensation offset of any indoor unit. The adjusted value is
programmed into the EEPROM.
Guide 1
1. Install the grille assembly and connect the power cable.
2. Unplug the wired controller.
3. Connect power to the unit.
4. Press the ON/OFF button on the remote control (HBS-01).
5. (Ignore this step if the display temperature is already
O
C,) Press MENU/OF button to switch the display temperature to
O
C,
then press confirm.
6. Open the front cover of the remote controller, and press the LIGHT button 12 times in 7 seconds.
7. The panel will beep 4 times and display an “A”.
8.
Press the LIGHT button once to confirm. The display will read “A0”.
9. Press the button TEMP. or TEMP. until the display shows “A5”.
10.
Press the LIGHT button once to confirm. The display will read “0b”.
11. Press the button TEMP. or TEMP. to scroll through the listed
Codes. Each code is associated with a corresponding compensation
value (see table below). For example, if you want make the
temperature invalid, scroll it to 0F.
12.
Press the LIGHT button once to confirm. The display will read “A5”.
13. Press the ON/OFF button on the remote control to save the changes.
Series
IDU
IDU PCB part number
Controls Needed
Guide
Reference
Haier
GEA
Controller
IR Reciever
Wired Controller
3X3 Cassette
AL24LP2VHA
0151800208
WJ26X23559
YR-HBS01
\
Unplug
1
2X2 Cassette
AB09SC2VH*
0151800208A
WJ26X23785
YR-HBS01
\
Unplug
3
2X2 Cassette
AB12SC2VH*
0151800208A
WJ26X23785
YR-HBS01
\
Unplug
3
2X2 Cassette
AB18SC2VH*
0151800208A
WJ26X23785
YR-HBS01
\
Unplug
3
Mid-Static Duct
USYM09UCDSA
0151800580
WJ26X27175
YR-HG
RE-02(CN29)
Unplug
4
Mid-Static Duct
USYM12UCDSA
0151800580
WJ26X27175
YR-HG
RE-02(CN29)
Unplug
4
Mid-Static Duct
USYM18UCDSA
0151800580
WJ26X27175
YR-HG
RE-02(CN29)
Unplug
4
Mid-Static Duct
USYM24UCDSA
0151800580
WJ26X27175
YR-HG
RE-02(CN29)
Unplug
4
Slim Duct
AD07SL2VH*
0151800175A
WJ26X23178
YR-HBS01
RE-02(CN29)
Unplug
2
Slim Duct
AD09SL2VH*
0151800175A
WJ26X23178
YR-HBS01
RE-02(CN29)
Unplug
2
Slim Duct
AD12SL2VH*
0151800175A
WJ26X23178
YR-HBS01
RE-02(CN29)
Unplug
2
Slim Duct
AD18SL2VH*
0151800175A
WJ26X23178
YR-HBS01
RE-02(CN29)
Unplug
2
Highwall
ASYW07URDWA
A0011001066
WJ26X25213
YR-HG
\
\
4
Highwall
ASYW09URDWA
A0011001066
WJ26X25213
YR-HG
\
\
4
Highwall
ASYW12URDWA
A0011001066
WJ26X25213
YR-HG
\
\
4
Highwall
ASYW18URDWA
A0011007590
WJ26X25413
YR-HG
\
\
4
Console
USYF09UCDWA
0151800579
WJ26X27223
YR-HG
\
\
4
Console
USYF12UCDWA
0151800579
WJ26X27223
YR-HG
\
\
4
Console
USYF18UCDWA
0151800579
WJ26X27223
YR-HG
\
\
4
Содержание AB09SC2VHA
Страница 2: ...Oct 2020 Manual release Revision History ...
Страница 12: ... This page intentionally left blank ...
Страница 45: ...WALL MOUNT TECHNICAL OVERVIEW ENGLISH Topic Title C 9 Wiring Diagrams ...
Страница 68: ... This page intentionally left blank ...
Страница 78: ... This page intentionally left blank ...
Страница 104: ... This page intentionally left blank ...