Preparation for Installation
M.3
If the transformer and monitoring product (mounted to the transformer using the GE
Direct Mount Cradle) are to be reengaged after transportation in situ, then the following
steps must be taken:
M.3.1
Remove the exterior isolator locks
The exterior isolator locks must be removed after transit and before the product is
powered on.
M.3.1.1
Bottom isolators
Loosen the nut at the front of the bottom isolator with a 10 mm nut spinner as
shown in Figure M—18.
Loosen the outer nut at the back of the bottom isolator with a 10 mm spanner as
shown in Figure M—19.
Note: Remove and retain this nut for future use.
Figure M—18: Loosen isolator front nut with nut
spinner
Figure M—19: Loosen isolator rear outer nut with
spanner
Loosen the inner M6 nut of the bottom isolator with a 10 mm spanner and
remove all fittings as shown in Figure M—20.
Note: Retain nut and washer for future use.
Pull down on the bottom locks to remove them.
Figure M—20: Bottom isolator with fittings removed
Repeat for the other bottom isolator.
Inner M6 nut
Spanner on outer
M6 nut
Lug
Large washer
Note: No nuts or
washers required