The reaction changes the chemical makeup of the oil before it reaches the sensor in
the product. This causes the product to measure acetylene and possibly other
gasses inaccurately.
Although a transformer already contains copper, GE Energy’s diagnostic and monitoring
equipment is designed to accurately measure the gasses in the oil of the transformer
without affecting that oil.
GE will not guarantee or perform warranty work on a product that has been
installed using copper tubing or any other tubing, other than stainless steel, as
specified above.