MA-005 - MINITRANS Installation Manual - Rev 3.1
29-Sep-15
Page 30 of 85
The outer sheath of the mains supply cable shall continue into the equipment
as far as possible, so that reinforced insulation is maintained between the
operator and mains supply.
The mains supply shall be connected so that the protective earth wire is the last
wire to take the strain and break free in the event of the cord being pulled.
The product has an M8 earth stud located on the bottom of the enclosure on
the right-hand side. To ensure continued safety and EMC compliance, this must
be connected to earth ground in accordance with local wiring regulations and
using at least 6 mm
2
(10 AWG) wiring (see Figure 9—4).
Figure 9—4: Earth terminal on bottom of enclosure
If heat trace is to be used, please refer to Appendix J.
9.2
Battery
The product uses a non-rechargeable lithium coin cell battery (Panasonic CR2450 3 V 620
mAh) as shown in Figure 9—5. In the event that the battery needs to be replaced, data
from the product must be backed up. Failure to do so may result in historical data loss.
Figure 9—5: Coin cell battery
MINITRANS Casing
Two cable glands
(one in front and
one behind)